Safety & Symbols; Safety Precautions - Afore HNS7000TL Installation And Operation Manual

On-grid pv inverter
Hide thumbs Also See for HNS7000TL:
Table of Contents

Advertisement

Circuit Breaker and Surge Protector Recommendation:
Type
Single-Phase(Two MPPT Trackers)
HNS7000TL
HNS8000TL
HNS9000TL
HNS10000TL
SPD: Lightning protection system, refer to the following options:
• AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage AC 305V.
• DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage DC 600V.
Note:
The Inverter can be only connected to low-voltage grid.
(220 / 230 / 240Vac,50 / 60Hz).
2. Safety & Symbols

2.1 Safety Precautions

1. All work on the inverter must be carried out by qualified electricians. And ensure
that children cannot access to the inverter.
2. The PV generator and inverter must be connected to the ground separately in
order to reach maximum protection for property and persons.
3. Do not touch cover until five minutes after disconnecting all sources of supply.
This is because the charge stored in capacitors may result a risk of electric shock.
4. The enclosure of Inverter can become hot during operation. To reduce the risk of
injury, do not touch the cover, heat sink at the back of the PV-Inverter or nearby
surfaces while Inverter is operating.
Max AC Current [A]
33.6
38.3
45
50
Safety & Symbols
Rated current of AC breaker[A]
63A
63A
100A
100A
02