Safety & Symbols; Safety Precautions - Afore HNS7000TL Installation And Operation Manual

On-grid pv inverter
Hide thumbs Also See for HNS7000TL:
Table of Contents

Advertisement

Circuit Breaker and Surge Protector Recommendation:
Type
Max AC Current [A]
Single-Phase(Two MPPT Trackers)
HNS7000TL
HNS8000TL
SPD: Lightning protection system, refer to the following options:
AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 2.5KV
DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 3.2KV
The wiring distance between the inverter and the distribution box should be at
least 5 meters.
Note:
The Inverter can be only connected to low-voltage grid.
(220/230Vac, 50/60Hz).
2.Safety & Symbols

2.1 Safety Precautions

1. All work on the inverter must be carried out by qualified electricians.
2. The device may only be operated with PV panels.
3. The PV panels and inverter must be connected to the ground.
4. Do not touch the inverter cover until 5 minutes after disconnecting both DC and
AC power supply.
Safety & Symbols
Rated current of AC breaker[A]
32
35.5
02
50
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hns8000tl

Table of Contents