User Manual S7comm / EtherNet/IP Slave
Document code: MN67627_ENG
Revision 1.000
Page 24 of 30
Industrial Electronic Devices
2) Edit the settings of the new Generic Ethernet Module. As shown in the screen shot
below, the module was named "HD67871" and the IP-address assigned is 192.168.0.5.
For the Comm Format "Data – SINT" shall be selected as the data type.
RSLogix 5000 requires a configuration assembly instance. Both modules do not provide a
configuration assembly instance. Therefore it is allowed to select an instance of 3 and to
set the value to zero.
3) The setting of 10msec for the "Requested Packet Interval (RPI)" is adequate but it
is possible to change this value as required. A lower value of 2ms shall not be selected.
Warning:
The field "Use Unicast Connection over EtherNet/IP" must be checked.
ADFweb.com S.r.l.