High Alarm Relative Temperature AL HI
This parameter is used to establish the relative temperature at which a high
temperature alarm condition will occur. When Average Temperature is
above the Main Set Point + High Alarm Relative Temperature, a high
temperature alarm condition will occur. This limit may be affected by the
Outside Probe if that probe is used and the Relative Outside
Temperature Alarm is set to a value other than
adjusted in 0.1° increments from 0.5°F to 40.0°F (0.3°C to 22.2°C).
Critical High Alarm Crit
This parameter is used to establish the temperature set point at which a
high temperature alarm condition will occur regardless of the Outside
Probe reading. When the Average Temperature is above this parameter, a
high temperature alarm condition will occur. Setting this parameter to
OFF will deactivate the critical high alarm check. This parameter is
adjusted in 0.1° increments from -40.0°F to 119.9°F (-40.0°C to 48.8°C),
OFF.

Average / Probes (POS 12)

Average Temperature
This parameter displays the actual average temperature of all activated
inside probes. The average is made from the inside temperature probes
whose DIP SWITCH is set to the ON position (see DIP Switches and Slide
Switches Table page 38). The Average Temperature is displayed to the
nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
Probe 1 P :1
This parameter displays the actual probe 1 temperature. The Probe 1
temperature is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C).
Probe 2 P :2
This parameter displays the actual probe 2 temperature. This parameter will
appear only if DIPSW2 is set to the ON position (see DIP Switches and
Slide Switches Table page 38). The Probe 2 temperature is displayed to
the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
Probe 3 P :3
This parameter displays the actual probe 3 temperature. This parameter will
appear only if DIPSW3 is set to the ON position (see DIP Switches and
Slide Switches Table page 38). The Probe 3 temperature is displayed to
the nearest 0.1° from -58.0°F to 140.0°F (-50.0°C to 60.0°C).
MST-5C
MST-5C USER'S GUIDE
www.monitrol.com
OFF. This parameter is
Section C-29