Connection Of The Room Thermostat; Fitting Of The Control Unit; App Installation (F 210, F 310) - oventrop ClimaCon F Series Operating Instructions Manual

Table of Contents

Advertisement

ClimaCon F
Installation
6.4.1.6 ClimaCon F 310 (24 V) (item no.1155531)
Terminal
Assignment
1
IN (L1 24 V AC) operating voltage
2
IN (L2 24 V AC) operating voltage
3
OUT (L1 24 V AC) two point / PWM
4
OUT (L1 24 V AC) setback output
5
IN (L1 24 V AC) change-over
6
IN (A) ext. 10K NTC
7
IN (B) ext. 10K NTC
8
OUT (signal) 0-10 V
OUT (NO) potential-free contact
9
(max 24V, 90mA DC/AC)
OUT (COM) potential-free contact
10
(max 24V, 90mA DC/AC)
1
2
3
4
L1
L2
L1
SELV
L2

6.4.2 Connection of the room thermostat

NOTICE
Damage to the ClimaCon due to several outer
conductors (phases) in the installation
!
Use the same outer conductor (phase) for
terminals 1 (operating voltage), 4 (setback input
or setback output) and 5 (change-over).
If this is not possible on site, ensure the
separation of the phases by means of a coupling
relay.
WARNING
Only ClimaCon F 310 (24 V) (item no. 1155531)
Danger to life due to excessive voltages at the
terminals for potential-free contacts
!
Only apply extra-low voltages (SELV) to
terminals 9 and 10.
f
Connect the cores to the terminal strip according to the
terminal assignment for your product variant (stripping
length 6 mm).
115500983-V02.01.2022
5
6
7
8
9
10
CO S1
NO
0 -10
COM
DI
(ON/
OFF)

ϑ
NTC
10 K
AI
L1
(0-10V)
L1

6.4.3 Fitting of the control unit

NOTICE
Damage to the device due to incorrect operating
voltage
Base plates and operating elements of the different
product variants are not compatible with each
other.
!
Only combine components of the same product
variant with each other.
f
Connect the control unit to the base plate by first
placing the control unit on the lower edge of the base
plate and then pressing it on with a slight twisting
motion.
Z
The room thermostat is completely mounted when
the release clip is audibly engaged.
Fig. 9:
Fitting of the base plate
6.5

App installation (F 210, F 310)

The ClimaCon F app is available for both Android
and iOS.
Note the minimum requirements regarding the
version of the operating system and the
Bluetooth version (see par. 3.5 on page 10).
1
Go to the Appstore for your operating system.
2
Search for the Oventrop App "ClimaCon" and install it.
15

Advertisement

Table of Contents
loading

Table of Contents