Change of position of the
vertical/horizontal terminals
Clearances Information on clearances is available on the website:
Phase separators Phase separators are mandatory for the 2ps configuration while insulation barriers to segregate the live parts
Connection to the power circuit The connection of a circuit-breaker to the power circuit is performed using the connection busbars of the
28 | © 2021 ABB | 1SDH002083A1002 - ECN000119014 - Rev. A
The circuit-breaker is supplied with single-tang terminals (IEC/UL Figure 58 UL and Figure 59 UL) or multi-
tang (only for IEC Figure 60 IEC and Figure 61 IEC).
Changing from horizontal to vertical and vice versa can be achieved at any time with these rear terminals,
with the exception of versions E4.2 UL 2500A and 3200A. Tighten the M8 screws with tightening torque =
20 N m - 177 lb in.
Figure 58 UL
Figure 60 IEC
http://www.abb.com/abblibrary/DownloadCenter/
The following layout is also available
can be positioned in the 4ps configuration.
Phase separators are mandatory if, between two phases, the minimum distance between the screws that fix
the circuit-breaker terminals to the connection bars is less than 14 mm - 0.55".
Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
particular with the kit sheet 1SDH001000R0810.
electric switchgear fixed to the terminals of the circuit-breaker. The sizing of the busbars is specified by the
designer of the electrical switchgear.
Figure 62
Figure 59 UL
Figure 61 IEC
- Cubicle Emax E4.2
1SDH001301R0001
ABB | SACE Emax 2
Continued on the next page
Management operations | 5 - Installation