Changing The Function Of The Receiver Unit By Sw2 - Delta DE212 GLOBAL Operation And Installation Manual

Wireless deadman system with differential pressure switch function for aero plane refuelling trucks and dispensers
Table of Contents

Advertisement

2.3 C
HANGING THE FUNCTION OF THE RECEIVER UNIT BY
The function of the receiver unit can be changed according to operational requirements.
The following can be changed:
SW2-1: Timed or no timed Deadman. ON is activated.
SW2-2: Simultaneous or no simultaneous operation of the extra function, connection P1-3 when the
Deadman is activated.
SW2-3: External override, active or off
-4: Differential Pressure Switch on or off.
SW2
Standard factory setting of SW2 switches:
OFF
ON
1
2
3
4
To change the settings:
1.
Set the function switch, SW2 to the desired position
2.
Take out the fuse, F1.
3.
Press the receiver front button CODE while replacing the fuse. Press the CODE button for about 3
seconds, then the function is changed according to settings.
4.
NOTE: SW2-2 must ALWAYS be set back to OFF after settings are changed.
SW2 Switch for function selection
NOTE: The connector for external override and STOP is normally not installed
This functions must be specified when ordering, see page 7.
D
RC AS
ELTA
SW2.
.
1.
Deadman timer enabled, 2 min timer (Default ON)
2. Simultaneous operation of extra function (Default OFF)
3. Deadman override input disabled (Default ON)
4. DP Enabled (Default ON)
User and Installation Manual, DE212 GLOBAL
Page 8 of 36
Document 02743