Economizer Module Wiring Details - Bryant 580J*04A Installation Instructions Manual

580j legacy series single package rooftop with gas heat/electric cooling sizes 04, 05, 06, 07
Table of Contents

Advertisement

Inputs
Sensors
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb
change over or an OA bus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional
Return Air (RA) bus sensor can be added to the system for dif-
ferential enthalpy or dry bulb changeover. For differential dry
bulb changeover a 20k ohm sensor is required in the OA and a
bus sensor in the RA. DIP switch on RA bus sensor must be
set in the RA position.
Dry Bulb Temperature (optional) and Mixed Air (required),
20k NTC
2-wire (18 to 22 AWG);
Temperature range -40 to 150°F (-40 to 65°C)
Temperature accuracy -0°F/+2°F
Temperature and Humidity, C7400S1000 (optional)
S-Bus; 2-wire (18 to 22 AWG)
Temperature: range -40 to 150°F (-40 to 65°C)
Temperature accuracy -0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) S-Bus sensors may be connected to the
W7220 economizer module. For outdoor air (OA), return air
(RA) and discharge (supply) air (DA).
4 Binary Inputs
1-wire 24 Vac + common GND (see page 24 for wiring
details).
24 Vac Power Supply
20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
Outputs
Actuator Signal
2-10 Vdc; minimum actuator impedance is 2k ohm; bus
two-wire output for bus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
Environmental
Operating Temperature
-40 to 150°F (-40 to 65°C).
Exception of display operation down to -4°F with full
recovery at -4°F from exposure to -40°F
Storage Temperature
-40 to 150°F (-40 to 65°C)
Shipping Temperature
-40 to 150°F (- 40 to 65°C)
Humidity
5% to 95% RH non-condensing
ECONOMIZER MODULE WIRING DETAILS —
Use Fig. 37 and Tables 9 and 10 to locate the wiring terminals
for the Economizer module.
NOTE: The four terminal blocks are removable. Slide out each
terminal block, wire it, and then slide it back into place.
MAT
MAT
OAT
OAT
S-BUS
S-BUS
IAQ 2-10
IAQ COM
IAQ 24V
ACT 2-10
ACT COM
ACT 24V
50040839-001
Rev. G
Fig. 37 — W7220 Wiring Terminals
S-Bus Sensor Wiring — The labels on the sensors and con-
troller are color coded for ease of installation. Orange labeled
sensors can only be wired to orange terminals on the controller.
Brown labeled sensors can only be wired to S-bus (brown) ter-
minals. Use Fig. 37 and Table 9 to locate the wiring terminals
for each S-Bus sensor.
Use Fig. 37 and Table 10 to set the DIP switches for the de-
sired use of the sensor.
Table 9 — Economizer Module - Left Hand Terminal
LABEL
TYPE
Top Left Terminal Block
MAT
20k NTC
MAT
and COM
OAT
20k NTC
OAT
and COM
S-BUS
S-BUS
S-BUS
(Sylk* Bus)
Bottom Left Terminal Block
IAQ 2-10
2-10 vdc
IAQ COM
COM
IAQ 24V
24 vac
ACT 2-10
2-10 vdc
ACT COM
COM
ACT 24v
24 vac
* Sylk is a trademark of Honeywell International Inc.
23
NA
MA
AUX2-
NA
MA
OCC
A2
OA
OC C
E-GND
OA
EXH1
EX
SB
SB
A1
AUX1-O
SB
SB
Cert
Product
California Title 24, Part 6
HJW10
SB
SB
www.energy.ca.gov
V
Y2-
Y2I
C
R
Y2O
Y2-O
Y1I
Y1-
V
Y1O
C
R
Y1-O
C
NA
R
C
R
50048848-002
Rev. A
Blocks
DESCRIPTION
Mixed Air Temperature Sensor (Polarity
Insensitive Connection)
Outdoor Air Temperature Sensor
(Polarity Insensitive Connection)
Enthalpy Control Sensor
(Polarity Insensitive Connection)
Air Quality Sensor Input (e.g. CO
sensor)
Air Quality Sensor Common
Air Quality Sensor 24 vac Source
Damper Actuator Output (2-10 vdc)
Damper Actuator Output Common
Damper Actuator 24 vac Source
2