3.4
PROFIBUS DP interface (SIMOTION D410 DP only)
SIMOTION D410 DP provides one interface to connect to PROFIBUS DP. The interface can
be run asynchronously or isochronously, equidistant.
A baud rate of up to 12 Mbps can be set for the PROFIBUS DP interface.
SIMOTION D410 includes master and I-slave functionality.
Note
If a SIMOTION D410 DP is operated as a passive PROFIBUS I-slave, the display,
measuring functions, and controller optimization engineering functions will be very slow. If
possible, use the "active I-slave" setting for local commissioning (which does mean that an
equidistance is no longer possible) and for complete commissioning, switch to "passive I-
slave".
Interface features
Table 3- 8
Features
Connector type
Cable type
Maximum cable length
Maximum data rate
Interface assignments
Table 3- 9
Interface assignment X21
View
D410
Manual, 05/2009
Interface X21
Pin
Name
1
-
2
M24_SERV
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP
7
P24_SERV
8
RxD/TxD-N
9
-
3.4 PROFIBUS DP interface (SIMOTION D410 DP only)
Type
9-pin D-Sub socket
PROFIBUS cable
100 m at 12 Mbps
12 Mbps
Description
unassigned
Teleservice supply, ground
Receive/transmit data P (B)
Control signal
PROFIBUS data reference potential
Supply voltage plus
Teleservice supply, + (24 V)
Receive/transmit data P (N)
unassigned
Interfaces
Area
0 V
RS485
TTL
5 V +/- 10 %
24 V (20.4 V - 28.8 V)
RS485
43