6 Technical data
6.6.5 eSy-Web communication
Interface:
Function:
IP address:
Subnet screen:
The actuator and the PC must be in the same network to use the web server. The IP address of the actuator is entered in the
web browser and the actuator can then be parametrised. In order to use more than one actuator, a definitive IP address must be
assigned to each actuator in the same network.
6.6.6 Modbus TCP communication
Interface:
IP address:
Subnet screen:
Port:
Supported function
codes:
GEMÜ SU60 SUMONDO
Ethernet
Parameterisation via web browser
192.168.2.1 alterable via web browser
255.255.252.0 alterable via web browser
Modbus TCP
192.168.2.1 alterable via web browser
255.255.252.0 alterable via web browser
502
Code Dezimal
3
4
6
16
23
Code Hex
0x03
0x04
0x06
0x10
0x17
16 / 36
Function
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple Registers
Read/Write Multiple Registers
www.gemu-group.com