Assembling The Motorized Actuator In The Housing - GEM SU60 SUMONDO Operating Instructions Manual

Motorized actuator for single-use valves
Table of Contents

Advertisement

10 Installation in piping
Only apply media pressure to the single-
use diaphragm valve body when it is
mounted on the motorized actuator.
▶ Otherwise the single-use diaphragm
valve body may be damaged.
Suitability of the product!
▶ The product must be appropriate for the piping system
operating conditions (medium, medium concentration,
temperature and pressure) and the prevailing ambient
conditions.
Tools
▶ The tools required for installation and assembly are not
included in the scope of delivery.
Use appropriate, functional and safe tools.
1. Ensure the product is suitable for the relevant application.
2. Check the technical data of the product and the materials.
3. Keep appropriate tools ready.
4. Use appropriate protective gear as specified in the plant
operator's guidelines.
5. Observe appropriate regulations for connections.
6. Have installation work carried out by trained personnel.
7. Shut off plant or plant component.
8. Secure the plant or plant component against recommis-
sioning.
9. Depressurize the plant or plant component.
10. Completely drain the plant or plant component and allow it
to cool down until the temperature is below the media va-
porization temperature and cannot cause scalding.
11. Correctly decontaminate, rinse and ventilate the plant or
plant component.
12. Lay piping so that the product is protected against trans-
verse and bending forces, and also from vibrations and
tension.
13. Only install the product between matching aligned pipes.
14. Optional installation position.
GEMÜ SU60 SUMONDO
CAUTION
NOTICE
NOTICE

10.2 Assembling the motorized actuator in the housing

▶ The motorized actuators A are sup-
▶ Do not remove the mounting plate 4.
▶ Otherwise the manufacturer liability
▶ Maximum thickness of the housing 5: 10 mm
Rework the housing before assembling the motorized actu-
ator A according to the borehole pattern below, so that the ac-
tuator's mounting plate 4 can be screwed on from above or
from the inside of the housing.
Preparation of the housing 5
1. Push the actuator on the clamp side from the inside
through the prepared plate opening of the housing (pre-
pared by the customer) as far as it will go (mounting
plate).
ð Take care to ensure that the seal supplied with the
product is correctly positioned. For example, the seal
prevents dust and cleaning fluids from penetrating in-
side the customer's unit.
Fig. 5: Borehole pattern for housing
(housing not included)
24 / 36
CAUTION
plied with a mounting plate 4 as stand-
ard.
and guarantee will be void.
NOTICE
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents