Connecting The Electrical Supply; Start-Up And Operation; Adjusting The Restrictor Manually; Version With Restrictor Plate) - Samson EB 3967 EN Mounting And Operating Instructions

Table of Contents

Advertisement

Start-up and operation

5.3.4
Connecting the electrical
supply
Î Connect the electrical power (voltage) as
shown in Fig. 8.
Fig. 8:
Terminal connection in the enclosure
6 Start-up and operation
The solenoid valve is ready for use after
mounting and start-up.
6.1 Adjusting the restrictor
manually (only K
version with restrictor
plate)
Restrictor plates with lock nut
Î Remove the cover protecting the lock nut
on the beveled corner of the restrictor
plate.
Î Undo the lock nut.
Î Adjust the actuating times:
− Turn the restrictor spindle clockwise
to reduce the cross-sectional area of
flow (slows the stroking speed).
− Turn the restrictor spindle counter-
clockwise to increase the cross-sec-
tional area of flow (increases the
stroking speed).
44
+
 0.32
VS
Î Fasten the restriction setting in place with
the lock nut.
Î Attach the cover protecting the lock nut.
Restrictor plates with safety plate
Î Loosen the two retaining screws on the
safety plate (restrictor plate side) and
push the plate to one side.
Î Adjust the actuating times:
− Turn the adjustment screw clockwise
to reduce the cross-sectional area of
flow (slows the stroking speed).
− Turn the adjustment screw counter-
clockwise to increase the cross-sec-
tional area of flow (increases the
stroking speed).
Î Push the safety plate back into its origi-
nal position (concealing the adjustment
screw). Fasten it in place with the two re-
taining screws.
Note
The construction of the restrictor plates suit-
able for SIL applications ensures that the
cross-sectional area of flow cannot be com-
pletely closed.
EB 3967 EN

Advertisement

Table of Contents
loading

Table of Contents