Fault Alarm And Countermeasures - Powtran PI500A-S Series Manual

Special solar inverter forwaterpump
Table of Contents

Advertisement

Personality parameter
y0.03
group display selection
Function code
y0.04
modification properties
y1 group Fault query parameter group
Code
Parameter name
y1.00 Type of the first fault
y1.01 Type of the second fault
y1.02 Type of the third(at last) fault
Frequency of the third(at last)
y1.03
fault
y1.04 Current of the third(at last) fault
y1.05 Bus voltage of the third fault
Input terminal status of the third
y1.06
fault
Output terminal status of the third
y1.07
fault
y1.08 Reserved
y1.09 Power-on time of the third fault
y1.10 Running time of the third fault
y1.13 Reserve
y1.14 Frequency of the second fault
y1.15 Current of the second fault
y1.16 Bus voltage of the second fault
Input terminal status of the second
y1.17
fault
Output terminal status of the second
y1.19
fault
Power-on time of the second
y1.20
fault
y1.23 Running time of the second fault
y1.24 Reserve
y1.25 Frequency of the first fault
y1.26 Current of the first fault
y1.27 Bus voltage of the first fault
Input terminal status of the first
y1.29
fault
Output terminal status of the first
y1.30
fault

9.Fault alarm and countermeasures

PI500A-S can provide effective protection when the equipment performance is played fully. In case of
abnormal fault, the protection function will be invoked, the inverter will stop output, and the fault code will be
displayed on the display panel of the inverter. Before consulting the service department, user can perform
self-check , analyze the fault cause and find out the solution according to the instructions of this chapter. If the
fault is caused by the reasons as described in the dotted frame, please consult the agents of inverter or directly
contact with our company.
No. Fault ID
Failure type
Inverter unit
1
Err.01
protection
Acceleration
2
Err.02
overcurrent
L group display selection(The same above)
Units digit:Reserved
Tens digit :User's change parameter display selection
0:Nodisplay
1:Display
0:Modifiable;
1:Not modifiable
0:Fault-free;
1: Inverter unit protection;
2: Accelerated overcurrent;
3: Deceleration overcurrent;
4: Constant speed overcurrent;
5: Accelerating overvoltage;
6: Decelerating overvoltage;
7:Constant speed overvoltage;
8: Control power failure;
9: Undervoltage;
10:Inverter overload;
11:Motor overload;
13: Output phase missing
14: Module overheating;
15: External fault;
16: Abnormal communication;
17: Abnormal contactor;
18: Abnormal current detection;
19: Abnormal motor self-learning;
21: Parametric read-write abnormality;
22: Inverter hardware abnormality;
23:Short circuit between motor and ground;
26:Running time arrives;
27: User-defined Fault 1;
28: User-defined fault 2;
29: Power-on time arrives;
31:The PID feedback is lost during
operation.
40:Fast current limiting timeout;
51:Initial position error;
COF: Communication failure
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Possible causes
1.The short circuit of inverter
output happens
2.The wiring for the motor and
the inverter is too long
3.module overheating
4.The internal wiring of inverter is
loose
5.The main control panel is
abnormal
6.The drive panel is abnormal.
7.The inverter module is abnormal
1.The acceleration time is too short
2.manual torque boost or V/F curve
17 / 20
Setting range
1.Eliminate peripheral faults
2.Additionally install the
reactor or the output filter
3.Check the air duct is
blocked or not and the fan is
working normally or not, and
eliminate problems
4.Correctly plug all cables
5.Seek for technical support
1.Increase acceleration time
2.Adjust manual torque boost
00
0
Factory
Change
setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Solutions