Types K5 and K6
To troubleshoot the valve and actuator, check for
the following: change in operating conditions; signal
failure; power failure; foreign matter lodged between
seat ring and plug; packing leakage.
Type SKD62U Electric Actuator
Principle of Operation
The actuator accepts a 0 to 10 Vdc, 0 to 135 or a 4
to 20 mA control signal. The actuator, mounted on
a valve, produces a stroke proportional to the input
signal. When power is turned off or the event of a
power failure, the actuator spring returns the valve to
its normal position.

Mounting and Installation

WARNING
Personal injury or system damage
may result if this electric atuator is
installed where service conditions
could exceed the limits given in the
Specifications section.
10
EA0410R1
Figure 10. Acceptable Mounting Positions
Installation, operation and maintenance
procedures performed by unqualified
personnel may result in improper
adjustment and unsafe operation. Either
condition may result in equipment
damage or personal injury. Only a
qualified person shall install or service
this electric actuator.
The vertical position is the recommended position
for mounting. The acceptable mounting positions are
shown in Figure 10.
Allow 4 in. / 100 mm around the sides and back of the
actuator and 8 in. / 200 mm above and to the front of
the actuator.
Detailed installation instructions for field mounting are
shipped with the actuator.
Startup
The valve body assembly determines the
complete assembly action.
Check the wiring for proper connections.
Note