6 Buffer memory
6.3.24 Power factor (Un \ G702, 703)
Stores the power factor.
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: -100000 to 100000 (-100.000 to 100.000%)
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
*The sign of the data is as shown in the following figure.
Regeneration lead
Regeneration lag
(b) Unit
×10
-3
%
(c) Update timing
It will be updated every measuring cycle (250 ms).
6.3.25 maximum power factor (Un \ G720, 721), minimum power factor (Un \ G726, 727)
The max./min. power factors are stored.
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: -100000 to 100000 (-100.000 to 100.000%)
*For the resolution, refer to Section 4.2.1.
(b) Unit
×10
-3
%
(c) Update timing
It will be updated every measuring cycle (500 ms).
90°
Consumption lag
180°
Consumption lead
270°
*Unit is fixed.
*Unit is fixed.