6 Buffer memory
6.2.10 Set Integrated value setting target (Un \ G51) and Integrated value setting value (Un \ G52, 53)
(1) Setting procedure
(a) Set the integrated value setting target in the buffer memory. Setting range is as follows:
(b) Set the integrated value setting value in the buffer memory.
- Configurable range: 0 to 999999999
- The unit used for the setting value is the same as that used for the electric energy and reactive
energy that are output to the buffer memory.
For details, refer to section 6.3.2.
(c) Turn Integrated value set request (YnC) from OFF to ON to enable* the setting.
(d) After checking that integrated value set completion flag (XnC) turns ON and setting is completed,
set the integrated value set request (YnC) to OFF.
Integrated value set request (YC)
積算 値セット完了 フラグ(X3)
Integrated value set Completion flag (XC)
(2) Default value
Integrated value setting target (Un\G51) is set to 0 (No set).
Integrated value setting value (Un\G52, Un\G53) is set to 0.
Setting value
0
1
2
3
After detected that the integrated value set request (YnC) turns OFF, the integrated value set
completion flag (XnC) turns OFF.
積算 値セット要 求(Y3)
O FF
O FF
Figure 6.2.10 Integrated value setting procedure
Description
No set
Electric energy (consumption)
Electric energy (regeneration)
Reactive energy (consumption lag)
ON
OFF
ON
OFF
6 – 13
QE81WH