9 Troubleshooting
Q
What kind of time is "response time"?
"Response time" is a period of time between a point of sudden change of voltage or current
input and a point that an output (computation result) follows up to within± 10 % of input.
A
9.3.3 Q&A about Installing
Q
What is wire diameter that allows installing a current sensor?
The nominal cross-sectional areas of the conductor of 600-V vinyl coated wires that can
penetrate (values for reference), refer to 7.5.3.1.
The above shows the standard nominal cross-sectional areas. Due to the outer difference of
A
finished vinyl insulation and deformation (bending) depending on manufacturers, a wire may
not penetrate.
Make verification on site.
Q
What are the points when installing a current sensor?
Models EMU2-CT5, EMU-CT*** and EMU-CT***-A are split-type. If split surfaces are not
A
engaged sufficiently or a foreign object exists between the split surfaces, adequate
performances are not obtained. Pay attention in installation.
100%
90%
Actual
value
Response
time
Measured value of the module
9 - 9
QE81WH
Time