6 Buffer memory
6.3.5 Multiplier of the electric current (Un \ G200)
The multiplier of the electric current is stored.
(1) Details of stored data
(a) Storage format
Data are stored as 16-bit signed binary in the buffer memory.
- Data range: -3 (fixed)
(b) Update timing
Because it is fixed at -3, there is no update.
6.3.6 1-phase current (Un \ G202, 203), 2-phase current (Un \ G204, 205), 3-phase current (Un \ G206, 207)
The electric current (effective value) of each phase is stored.
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: 0 to 99999990 (0 to 99999.990 A)
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Unit
×10
-3
A
(c) Update timing
It will be updated every measuring cycle (250 ms).
6.3.7 1-phase current demand (Un \ G210, 211), 2-phase current demand (Un \ G212, 213), 3-phase current
demand (Un \ G214, 215)
Stores the electric current (effective value) at each phase that is measured based on the moving
average for the duration of time configured in the electric current demand time (Un\G3).
(1) Details of stored data
(a) Storage format
Data are stored as double-word 32-bit signed binary in the buffer memory.
- Data range: 0 to 99999990 (0 to 99999.990 A)
*Restrictions for measured data including resolution and measuring range, refer to section 4.2.1.
(b) Unit
×10
A
-3
(c) Update timing
It will be updated every measuring cycle (250 ms).
*Unit is fixed.
*Unit is fixed.
6 – 17
QE81WH