Application Errors - Endress+Hauser Fieldbus Levelflex M FMP41C Operating Instructions Manual

Guided level-radar foundation fieldbus
Hide thumbs Also See for Fieldbus Levelflex M FMP41C:
Table of Contents

Advertisement

Levelflex M FMP41C with FOUNDATION Fieldbus
Error
Output
A warning or alarm
Depending on the configuration
has occurred.
Measured value
(00) is incorrect
No change off
measured value on
filling/emptying
E 641 (loss of
If the instrument is configured to Hold by loss of
echo) after turn on
echo the output is set to any value/current.
the power supply
Endress + Hauser
9.3

Application errors

20 mA/100%
F m/ft
expected
actual
E m/ft
4 mA/0%
L00-FMP4xxxx-19-00-00-en-019
20 mA/100%
actual
expected
4 mA/0%
L00-FMR2xxxx-19-00-00-en-014
Possible cause
See table of
error messages
(see Page 79)
Measured distance
(008) OK?
t ¡
no
An interference echo
may have been
evaluated.
Interference echo from
installations, nozzle
or extension on the
probe
t ¡
noise level during the
initialisation phase to
high.
Trouble-shooting
Remedy
1. See table of error messages
(see Page 79)
yes
1. Check empty calibr. (005) and
full calibr. (006)
2. Check linearisation:
level/ullage (040)
max. scale (046)
diameter vessel (047)
Check table
yes
1. Carry out tank mapping
basic setup
1. Carry out tank mapping
basic setup
2. If necessary, clean probe
3. If necessary, select better
mounting position
Repeat once more empty calibr.
(005).
Caution!
Before conformation change with
S
or
to the edit mode.
O
81