Endress+Hauser Fieldbus Levelflex M FMP41C Operating Instructions Manual page 70

Guided level-radar foundation fieldbus
Hide thumbs Also See for Fieldbus Levelflex M FMP41C:
Table of Contents

Advertisement

Commissioning
!
70
Basic Setup step 6/6:
• This step starts the tank mapping
• The measured distance and the current measured value are always displayed in the header
• for a description, see Page 61)
6.8.1
Blocking distance
Note!
Please reenter the blocking distance in the function "upper block.dist" (059) when installing the
device in a high nozzle: upper blocking distance (UB) = nozzle height (H) + 50 mm.
Levelflex M FMP41C with FOUNDATION Fieldbus
H
UB
50
l00-fmp4xxxx-20-00-00-en-004
L00-FMP4xxxx-14-00-06-xx-001