TEMPERATURE CONTROLLER
UTC-221P
PV = Process Value
SV = Set Value
TECHNICAL SPECIFICATION
INPUT SPECIFICATION:
Input
Range
J
0 to 600°C,
Input Types
K
0 to 1200°C,
PT-100
-99 to 400°C,
PT.1
-99.9 to 400.0°C,
J,K,PT-100 = 1°C
Resolution
PT.1 = 0.1°C
±1% of FSD ± 1°C
Indication
Accuracy
(FSD:- Full Scale Deflection)
DISPLAY AND KEYS:
Upper: 4 digit, 7 segment, 0.70" Red
Display
Lower: 4 digit, 7 segment, 0.50" Green
Keys
SET, INC, DEC, ENT
DIMENSION:
Size
72 (H) x 72 (W) x 85 (D) mm
Panel Cutout
68 (H) x 68 (W) mm
CONTROL METHOD:
CONTROL METHOD:
1) PID control with Auto-Tuning
Heating
2) ON-OFF control
Cooling
ON-OFF control
OUTPUT SPECIFICATION:
Relay Output
Relay
1 Nos
Relay Type
1C/O (NO-C-NC)
Rating
10A, 230V AC / 28V DC
SSR Drive Output
12V DC, 30mA DC
(On-Off condition)
Output Signal
Relay parallel to SSR
POWER SUPPLY:
Supply
100 to 270V AC, 50-60Hz
Voltage
Power
Consuption
4VA @ 230V AC MAX
(VA Rating)
ENVIRONMENT CONDITION:
Operating Temp.
0°C to 55°C
UP to 95% RH
Relative Humidity
(non-condensing)
Protection Level
IP-65 (Front side) As per IS/IEC
(As per request)
60529 : 2001
MECHANICAL INSTALLATION
Panel Cutout
Outline Dimension (mm)
Dimension (mm)
UTC 221P
ºC
3 2 4
PV
68
R
235
72
SV
TUNE
SET
ENT
85
68
72
3
TERMINAL CONNECTION
L
1
8
~
100
270V AC
TC
50/60 Hz
2
N
9
4VA
-
!
RTD
3
10
NO
Made in India
4
11
C
RELAY1
NC
5
12
-
6
13
O/P
S.S.R
7
14
www.multispanindia.com
Sensor Input
8
8
9
9
Install jumper
when using
10
10
2 Wire RTD
3-Wire RTD
2-Wire RTD
8
9
Thermocouple
STATUS LED DESCRIPTION
2 345
1
2500
3
2
1 - Control output indication
2 - Auto tuning "ON" indication
3 - Blinking DP Will Indicate Delay time Count
KEY OPERATION
FUNCTION
PRESS KEY
OPERATOR MODE
To enter in parameter setting
For start/stop PID auto tuning
To go in factory setting mode
+
Press 3 sec
PARAMETER SETTING MODE
To set parameter value
To increment parameter value.
To decrement parameter value.
Set parameter to be save & exit.
SAFETY PRECAUTION
!
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
WARNING GUIDELINES
WARNING : Risk of electric shock.
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance
Ω
(5 max per line) and no resistance differentials among
three wires should be present.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
INSTALLATION GUIDELINES
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
Press
and internal wiring.
6 sec
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power 'ON'
or 'OFF' function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
MECHANICAL INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage
of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
Page 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the UTC-221P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MULTISPAN UTC-221P

  • Page 1 POWER SUPPLY: TEMPERATURE CONTROLLER STATUS LED DESCRIPTION WARNING GUIDELINES UTC-221P Supply 100 to 270V AC, 50-60Hz WARNING : Risk of electric shock. Voltage 2 345 Power 1. To prevent the risk of electric shock, power supply to the Consuption 4VA @ 230V AC MAX...
  • Page 2 Auto Tuning:- Control Parameter ERROR DISPLAY PARAMETER SETTING The Auto-tuning function automatically computes When an error has occurred the display indicates error codes and sets the Proportional band (Pb) , Integral time (It), Password To ENTER CONTROL as given below. Derivative time (dt), and cycle time as per process Message PARAMETER...