5. Standard specifications

Items
Rated voltage
Input frequency
Power Input
Allowing fluctuations
Control system
Control method
Automatic torque
boost function
Acceleration/decal
eration control
V/F curve mode
Over load capability
Maximum frequency 1.Vector control:0 to 300Hz; 2.V/F control:0 to 3200Hz
Carrier Frequency
Input frequency
resolution
Control
Start torque
Speed range
Steady-speed precision Vector control W/O PG: ≤ ± 0.5% (rated synchronous speed)
Torque response
Torque boost
DC braking
Jogging control
Built-in PID
Automatic voltage
regulation(AVR)
Self-inspection
ofperipherals after
power-on
Common DC bus
Personalization
function
Quick current limiting The current limiting algorithm is used to reduce the inverter over
Timing control
Input
signal
Running
Output
Signal
Running command
channel
Frequency source
Run function
Protection
Inverter protection
function
LED
display
keyboa rd
Display
Key lock and function
selection
IGBT temperature
Communi cation RS485
Environment
temperature
Storage temperature
Environment
humidity
Enviroment
Vibration
Application sites
Altitude
Protection level
* Enter the menu screen step by step, set the parameter confirmation.
*This key function is determined by the function code F6.21.
* F0.03 setting to 4, and the keyboard potentiometer setting the
operating frequency.
AC 1PH 220V(-15%) to 240V(+10%)
AC 3PH 220V(-15%) to 240V(+10%)
AC 3PH 380V(-15%) to 440V(+10%)
AC 3PH 480V(-10%) to 480V(+10%)
50Hz/60Hz
Voltage continued
volatiliy:± 10%
Input frequency
fluctution:± 5%;
High performance vector control inverter based on DSP
V/F control, vector control W/O PG,
Realize low frequency (1Hz) and large output torque control under
the V/F control mode.
Straight or S-curve mode. Four times available and time range is 0.0
to 6500.0s.
Linear, square root/m-th power, custom V/F curve
G type:rated current 150% - 1 minute, rated current 180% - 2seconds
F type:rated current 120% - 1 minute, rated current 150% - 2 seconds
0.5 to 16kHz; automatically adjust carrier frequency according to the
load characteristics.
Digital setting: 0.01Hz Analog setting: maximum frequency*0.025%
G type: 0.5Hz/150% (Vector control W/O PG)
F type: 0.5Hz/100% (Vector control W/O PG)
1:100 (Vector control W/O PG)
≤ 40ms (Vector control W/O PG)
Automatic torque boost; manual torque boost(0.1% to 30.0%)
DC braking frequency: 0.0Hz to max. frequency, braking time:0.0 to
100.0 seconds, braking current value: 0.0% to 100.0%
Jog Frequency Range: 0.00Hz to max. frequency;Jog Ac/deceleration
time: 0.0s to 6500.0s.
Easy to realize closed-loop control system for the process control.
Automatically maintain a constant output voltage when the voltage
of electricity grid changes
After powering on, peripheral equipment will perform safety testing,
such as ground, short circuit, etc.
Multiple inverter can use a common DC bus.
current probability, and improve whole unit anti-interference capability.
Timing control function: time setting range(0m to 6500m)
DI input
6 digital input terminals, DI5 for high-speed pulse input(0 to 100
terminal
kHz square wave)
AI1 analog
1 analog input terminals respectively for optional range (0 to 20mA
input
or 0 to 10V), they can be used to set frequency, output frequency
At most 16-speed can be set(Run by using the multi-function
Multi-speed
terminals or program)
Emergency
Interrupt controller output
stop
When the protection function is active, you can automatically or
Fault reset
manually reset the fault condition.
PID feedback
Including DC(0 to 10V), DC(0 to 20mA)
signal
Output signal One way output SPA;One way contact output;One way AD1 analog
output
SPA contact
There are 40 signals each way .Contact capacity : normally open
output
contact 5A/AC 250V,1A/DC 30V.
DA1 analog
One way analog output,can select frequency, current ,voltage etc 16
output
singnals.Output signals can be sent 0 to 10V/0 to 20mA
Three channels: operation panel, control terminals and serial
communication port. They can be switched through a variety of
ways.
Total 8 frequency sources: digital, analog voltage,analog current ,
multi-speed and serial port. They can be switched through a variety of
ways.
Limit frequency, jump frequency, frequency compensation,
auto-tuning, PID control
Overvoltage protection, undervoltage protection, overcurrent
protection, overload protection, overheat protection, overcurrent stall
protection, overvoltage stall protection, losting-phase protection
(optional), communication error, PID feedback signal abnormalities,
PG failure and short circuit to ground protection.
Monitoring objects including: running frequency, set frequency,bus
voltage, output voltage, output current, output power, output torque,
Running
input terminal status, output terminal status, analog AI1 value,, motor
information
Actual running speed,PID set value percentage, PID feedback value
percentage.
At most save three error message, and the time, type, voltage,current,
Error
frequency and work status can be queried when the failure is
message
occurred.
Lock part or all of keys, define the function scope of some keys to
prevent misuse.
show the inverter inner IGBT temperature
Built in 485
-10℃to 40℃ (Temperature at 40 ℃to 50℃, please derating for use)
-20 ℃ to 65 ℃
Less than 90% R.H, no condensation.
Below 5.9m/s² (= 0.6g)
Indoor where no sunlight or corrosive, explosive gas and water
vapor, dust, flammable gas,oil mist, water vapor, drip or salt, etc.
No need degrade use under 1000m,degrade 1% for altitude rise 100m
when above 1000m,do not use it above 3000m
IP20
Specifications
Less than 3% of voltage unbalance rate 3%
Distortion satisfy IEC61800-2andard;
3 / 16