LED indication

Green LED indicates 24 V DC supply; it flashes during operation. If "run-in" is not used, this function must
be deactivated in the tool.
Yellow LED indicates control.
The flashing sequence indicates if the valve is closing or opening.
Red LED indicates high- or low-level alarm, depending upon the set-
up.
3-digit display: (not available on /S stepper motor control version.)
Showing 0...100 % linearly corresponding to 4...20 mA.
LED Signal
Green
Yellow
Red
Yellow + Red
All

Calibration on the sensor

Calibration instructions:
0% or 100% for calibration can be carried out independent of each other. We recommend only calibrating at 0% if a high
degree of accuracy is desired.
Note: To use this function the "Zero & span cal. Function " field found under basic settings have to be on - default is off
Instruction for 0% calibration:
Connect the supply cable
Empty the vessel
Activate "R" for 5 seconds to activate calibration mode = Yellow LED is on (ON) during the 5 second activation and
turns off (OFF) when calibration mode is activated.
Activate "R" once = Yellow LED flash once. Afterwards, the green LED flashes to confirm calibration.
Instruction for 100% calibration:
Fill the vessel to 100%.
Activate "R" for 5 seconds to activate calibration mode = Yellow LED is on (ON) during the 5 second activation and
turns off (OFF) when calibration mode is activated.
Follow the instructions under "Configurations Instructions" regarding the installation of drivers in the program.
Activate "R" twice = Yellow LED flashes twice. Afterwards, the green LED flashes to confirm calibration.
Wire level sensor manual 05
ON/OFF/Frequency
Functionality
ON
Supply voltage connected
Flash
Run In start signal / in operation.
OFF
No supply voltage
ON
Activation of valve control / and during calibration
OFF
Valve control not active
ON
Alarm, high or low level, depending upon the setup.
Flash slow
No contact to sensor probe or sensor probe shorted
Flash fast
USB cable connected and communication active
OFF
No alarm
Flash
Insufficient Power supply
Flash
USB cable connected and communication active
OFF
No alarm