Advanced settings
Here you make the advanced settings of the sensor
Here you set the parame-
ters for the alarm func-
tion.
Only available for sensors
without cable
Alarm relay function: Here, the relay function is indicated, depending upon
the instructions – NO or NC (normally open/normally closed). Here the signal
can be changed from alarm on below or above the alarm setpoint
Output direction: Here you select either LP-mode (low pressure control) or HP
-mode (high pressure control). In LP-mode, the container is filled so that the
level is maintained, and in HP-mode the container is emptied so that the level
is maintained. LP-mode = 4-20 mA. HP-mode = 20-4 mA.
Set mA or digital 2 output Select the sensor output digital or analog
Digital 2 alarm in %: set the alarm setpoint
Digital Hysteresis in %: %: Indicates the deviation required before the alarm is
deactivated, following activation of the alarm. Alarm hysteresis in percent of
the probes calibrated span 0 and 100%.
Alarm setting is as well in % of the probes calibrated span 0 and 100%.
E.g. alarm setting = 80%, Alarm hysteresis = 25%
Set LED indication: Determines the function LED lighting has.
Wire level sensor manual 05
October 2021 HBproducts.dk
Here you can adjust
parameters for the
valve control
15