Led Indications On Sensor Head; Use Of The Sensor With Other Refrigerants - HB Products HBX Installation And Configuration Manual

Vapor quality sensor, sensors for optimizing evaporator control, both for dx (direct expansion) and overfeed-systems, for compressor protection and leakage detection (ammonia carbamate)
Table of Contents

Advertisement

The LED indications on sensor head
The electronic element has build in LED's red, yellow and green and they will light up depending of the conditions and can be
used for diagnostics. The table shows the different indications:
LED light
Appearance
Green
ON
Flashing
OFF
Green and Red
Flashing Individually
Yellow
Flashing
Red
ON
Flashing (one pr. sec)
Flashing (two pr. sec.)
Red and Yellow
Flashing at the same time
(two pr. sec.)
Red, yellow and
Red Flashing (two pr. sec.)
green
Yellow flashing (one pr. sec)
Green constant on

Use of the sensor with other refrigerants

The sensor must be ordered for a specific refrigerant. It is possible to change the sensor to work with another refrigerant, but
a full package of new settings have to be uploaded. HB products has the setting files for most refrigerants and you can get
them on request. The refrigerant the sensor is specified for can be found under the basic settings tab. Please note that the list
of refrigerants is not complete and the sensor might be specified for instance for CO2 and can be used for R290 as an exam-
ple.
Contact HBproducts support if you need more information
Email:
support@hbproduct.dk
Telephone : +45 8747 6200
HBX-all types installation and calibration manual 03
Functionality
The HBX sensor is on. It gives analog feedback to the PLC, but it is
not controlling the expansions valve (the valve is turned off)
The sensor is on. It gives analog feedback to the PLC, and contros
the expansion valve (The sensor receives a Run-in signal (Digital
input))
The sensor is not receiving power
There is no connection between mechanical- and electrical part
The flashing sequence indicates if the valve is opening or closing:
Long time between flashes= The valve is barely open
Short time between flashes = The valve is "much" open
The ammonia is too wet
The sensor detects a lot of liquid. The sensor will give 22-24mA
The sensor is connected with USB-cable
The splitter box is connected
The sensor is connected with USB-cable
date: 26-06-2020
WWW.HBPRODUCTS.DK
24