HB Products HBPH-MK2 Instruction Manual

HB Products HBPH-MK2 Instruction Manual

Suited for brine/nh3 leakage detection differential 2-wire (4-20 ma) ph sensor

Advertisement

Quick Links

INSTRUCTION MANUAL
HBPH-MK2 - pH sensor
Suited for brine/NH3 Leakage detection
DIFFERENTIAL 2-WIRE (4-20 mA) pH Sensor
Salt bridge kit

TABLE OF CONTENTS

General Information ...................................................................................................................................................................... 2
Specifications ................................................................................................................................................................................. 2
Installation ..................................................................................................................................................................................... 3
Cold Liquid applications ................................................................................................................................................................. 3
Electrical connection ...................................................................................................................................................................... 4
Storage ........................................................................................................................................................................................... 4
Maintenance and calibration ......................................................................................................................................................... 4
Calibrating the Sensor .................................................................................................................................................................... 5
Checking the Sensor ....................................................................................................................................................................... 5
Probe Cleaning ............................................................................................................................................................................... 6
Replacement of Salt Bridge ............................................................................................................................................................ 7
Troubleshooting ............................................................................................................................................................................. 7
Parts and Accessories .................................................................................................................................................................... 8
Sensor Return ................................................................................................................................................................................ 8
Further Information ....................................................................................................................................................................... 8
Included in the package
Sensor with cable
Replacement salt bridge
Liquid for flushing and
filling

Advertisement

Table of Contents
loading

Summary of Contents for HB Products HBPH-MK2

  • Page 1: Table Of Contents

    INSTRUCTION MANUAL HBPH-MK2 – pH sensor Suited for brine/NH3 Leakage detection DIFFERENTIAL 2-WIRE (4-20 mA) pH Sensor Included in the package • Sensor with cable • Replacement salt bridge • Liquid for flushing and filling Salt bridge kit TABLE OF CONTENTS General Information ..................................
  • Page 2: General Information

    3,0 m/sec (10 ft/sec) Maximum Load 450 Ω Temperature Limits 6,9 barg (100 psig) @ 65 °C, 2,75 barg (40 psig) @ 95°C Power Supply Limit 24±4 VDC Cable 4.6 m (15 ft) Instructional manual- HBPH-MK2 – UK-004 Page 2...
  • Page 3: Installation

    0 to + 10°C . Instructional manual- HBPH-MK2 – UK-004 Page 3...
  • Page 4: Electrical Connection

    8 and pH below 6. The second level can then be an alarm at pH=9. With such a system it is not necessary to make frequent checks and calibrations, however we recommend an annual or biannual check of the calibration. Instructional manual- HBPH-MK2 – UK-004 Page 4...
  • Page 5: Calibrating The Sensor

    The operation of the 2-wire, 4-20 mA sensor can be checked by a few simple measurements. Two pH buffer solutions, 7 pH and either 4 pH or 10 pH, and a DC milliammeter are required. Instructional manual- HBPH-MK2 – UK-004 Page 5...
  • Page 6: Probe Cleaning

    5. Soak the probe for not more than 5 minutes in the chosen acid; then rinse thoroughly with clean warm water and soak in water for 3-5 minutes. 6. Calibrate the system in accordance with the instrument instruction manual. Instructional manual- HBPH-MK2 – UK-004 Page 6...
  • Page 7: Replacement Of Salt Bridge

    Replacement of Salt Bridge If the system cannot be calibrated after cleaning the probe, it may be necessary to replace the standard cell solution and/or the salt bridge. A salt bridge kit is available from HB Products for this purpose.
  • Page 8: Parts And Accessories

    -15°C. HB Products cannot be responsible for shipping damage or for damage due to frozen electrodes. For safety reasons, HB Products cannot accept probes which have not been thoroughly cleaned to remove all process material and put a piece of cotton ball with a few drops of water into the protective cap and place it on the sensor with tape to prevent it from drying out.