Connection diagram for sensors with control ca-
ble for modulating valve — here shown with Sie-
mens MVS661
Motor valve: 4-20 mA 24 V DC, max 24 W
3 wire connection
Wire level sensor manual 05
- = White common
+ = Brown Supply
AO = Grey , 4-20 mA
1
+24V DC or AC
2
- Common
3
AI Remote set point 4-20 mA
4
AO, 4-20 mA level
5
Run in signal
The sensor has a build in controller for a pulse modulating valve. The
sensor provides both the analog output via the cable to control the
valve. The level measurement signal for the PLC comes via the M12
plug .
On pin 3 it is possible to send an analog 4-20 mA signal to the controller
and change the setpoint. The signal is scaled linear like analog output.
The cable is connected according to the drawing and the parameters
are set as shown in the next section.
Suited for
HBSLT/C and HBSLT–wire & Flex/C
HBLC/C
MVS661 motor valve
G0
G
Y
M
U
ZC
Manual open/close
October 2021 HBproducts.dk
-common
+ supply
mA input
mA output position
Open/Close valve
+
PLC
-
AO
AI
DO
11