Installation Instructions—Flex sensor
The Flex sensor is designed for level measurement of liquids in
vessels like, tanks, pump separators and receivers . The sensor
can be mounted in a standpipe 1" (25mm) or 1 ¼" (32mm) diam-
eter or directly in a vessel with an inner pipe 1" (25mm) or 1
¼" (32mm) diameter. The inner pipe is needed to create suffi-
cient measuring signal and to avoid a swinging wire in a lively
fluid.
The following applies to the design of the system:
It must be installed in a vertical position
Sensor must have a minimum of 50 mm between the sensor weight end and the bottom of the pipe.
The sensor must be installed in an overflow or standpipe where the flow stream and turbulence are minimized.
The sensor must be mounted in a standpipe DN25 orDN32. The standpipe must be insulated to avoid boiling of refrig-
erant.
The outlet pipe from standpipe shall be mounted in an angle of 5-10 degree from horizontal to secure drainage and oil
pockets in refrigeration systems.
The sensor is supplied and can be is installed with a standard non-shielded cable.
If EMC is greater than described in EN 61326, a shielded cable must be used.
Wire level sensor manual 05
Standpipe should be insula-
ted to avoid boiling in stand-
Sensor must have a minimum
of 50 mm between the sen-
sor weight end and the
bottom of the pipe.
Drainpipe most be placed at
an angle of 5-10°, to avoid oil
pockets in standpipe.
October 2021 HBproducts.dk
5