Installation Instructions—wire sensor
The wire sensor is designed for level measurement of liquids in vessels like,
tanks, pump separators and receivers . The sensor can be mounted in a
standpipe from 1" (25mm) up to 4" (100mm) diameter or directly in a vessel
with an inner pipe from 1" (25mm) up to 4" (100mm) diameter. The inner
pipe is needed to create sufficient measuring signal and to avoid a swinging
wire in a lively fluid. To reduce wire movements in larger pipes a special
weight can be used.
The following applies to the design of the system:
It must be installed in a vertical position
Sensor must have a minimum of 50 mm between the sensor weight end and the bottom of the pipe.
The sensor must be installed in an overflow or standpipe where the flow stream and turbulence are minimized.
The sensor must be mounted in a standpipe bigger than DN25. Standpipe must be insulated to avoid boiling of refrig-
erant.
The outlet pipe from standpipe shall be mounted in an angle of 5-10 degree from horizontal to secure drainage and oil
pockets in refrigeration systems.
The sensor is installed and is supplied with a standard non-shielded cable.
If EMC is greater than described in EN 61326, a shielded cable must be used.
Wire level sensor manual 05
Standpipe should be insula-
ted to avoid boiling in stand-
Sensor must have a minimum
of 50 mm between the sen-
sor weight end and the
bottom of the pipe.
Drainpipe most be placed at
an angle of 5-10°, to avoid oil
pockets in standpipe.
Special weight for mounting in turbulent
conditions. The steel spacer "star" can be
shortened, using a simple tin cutting shear,
to fit the standpipe. Allow 2 mm play be-
tween inner pipe diameter and "star" di-
ameter
October 2021 HBproducts.dk