Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
Ed
X
X
F0
X
X
F1
X
X
F2
X
X
F3
X
X
F4
X
X
System char-
Cause
acteristics
Burner control
Internal fault
unit fault
Burner
Internal fault
blocked
Burner control
Flue gas
unit fault
temperature
limiter has
responded.
Burner control
The tem-
unit fault
perature lim-
iter has
responded.
Burner control
Flame signal
unit fault
is already
present at
burner start.
Burner control
No flame sig-
unit fault
nal.
Troubleshooting
Remedy
Replace the con-
trol unit.
Replace the con-
trol unit.
Check the heating
system fill level.
Vent the system.
Press reset but-
ton "E" after the
flue gas system
has cooled down.
Check the heating
system fill level.
Check the circula-
tion pump. Vent
the system.
Check the tem-
perature limiter
and connecting
cables.
Press "E".
Check the ionisa-
tion electrode and
lead.
Press "E".
Check the ionisa-
tion electrode and
lead, measure the
ionisation current,
check the gas
pressure, check
the gas combina-
tion valve, igni-
tion, ignition
module, ignition
electrodes and
the condensate
drain.
Press "E".