Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
E5
X
X
E8
X
X
E9
X
X
EA
X
X
Eb
X
X
EC
X
X
80
System char-
Cause
acteristics
Burner
Internal fault
blocked
Burner control
The ionisa-
unit fault
tion current
lies outside
the permissi-
ble range
Burner control
The ionisa-
unit fault
tion current
lies outside
the permissi-
ble range
during cali-
bration
Burner control
The ionisa-
unit fault
tion current
lies outside
the permissi-
ble range
during cali-
bration
Burner control
Heat draw-
unit fault
off repeat-
edly too low
during cali-
bration
Burner control
The ionisa-
unit fault
tion current
lies outside
the permissi-
ble range
during cali-
bration
Remedy
Check the ionisa-
tion electrode and
leads. Check the
flue gas system
for soundness.
Press "E" and re-
place the control
unit, if required.
Check the ionisa-
tion electrode and
lead.
Press "E".
Check the ionisa-
tion electrode and
lead.
Press "E".
Check the ionisa-
tion electrode and
lead.
Press "E".
Initiate heat draw-
off and trigger
manual calibra-
tion (see
page 91).
Press "E".
Check the ionisa-
tion electrode and
lead.
Press "E".