Type eva, dhw cylinders with peripheral indirect coils 130 to 200litre capacity

Advertisement

Installation instructions

for contractors
Vitocell 300 V and Vitocell 300 W
Type EVA
DHW cylinders with peripheral indirect coils
130 to 200 litre capacity
VITOCELL 300 V
VITOCELL 300 W
5592 783 GB
3/2007

Advertisement

Table of Contents
loading

Summary of Contents for Viessmann VITOCELL 300V

  • Page 1: Installation Instructions

    Installation instructions for contractors Vitocell 300 V and Vitocell 300 W Type EVA DHW cylinders with peripheral indirect coils 130 to 200 litre capacity VITOCELL 300 V VITOCELL 300 W 5592 783 GB 3/2007...
  • Page 2: Safety Instructions

    Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety regulations Before working on the equipment/ Installation, commissioning, heating system, isolate the power inspection, maintenance and repairs supply (e.g. by removing a separate mains fuse or by means of a main must only be carried out by a competent person (heating isolator) and safeguard against...
  • Page 3: Product Information

    Product information DHW cylinders with peripheral indirect coils for DHW heating in conjunction with freestanding and wall mounted boilers. 130, 160 and 200 litre capacity. Suitable for systems conforming to DIN 1988, EN 12 828 and DIN 4753. DIN registration number 0166/99 10 MC. Heating water return Heating water flow Cold water...
  • Page 4: Connecting The Earth Bonding

    DHW cylinder installation and levelling ¨ Install the DHW cylinder in a Please note room that is free from the risk of The thermal insulation must frost and draughts. Otherwise it not be able to come into must be drained when not in use contact with naked flames.
  • Page 5: Connection On The Heating Water Side

    Connection on the heating water side H Connect all pipes with detachable fittings. H Adjust the control thermostat and high limit safety cut−out to ensure that the DHW temperature inside the DHW cylinder never exceeds 95 ºC. Permiss. temperatures Test pressure H on the heating water side H on the heating water side 110 ºC...
  • Page 6: Connecting The Domestic Hot Water Side

    Connecting the domestic hot water side H For the connection on the DHW side, observe DIN 1988 and DIN 4753 [or local regulations]. H Equip the DHW circulation line with a circulation pump, check valve and a time switch. Only a limited gravity operation is possible. H Connect all pipes with detachable fittings.
  • Page 7 Connecting the domestic hot water side (cont.) Safety valve Equip the system with a type−tested The pipework between the safety diaphragm safety valve as protection valve and the DHW cylinder must not against overpressure. be restricted in any way. The safety Permiss.
  • Page 8 Commissioning For commissioning, see the service instructions Viessmann Werke GmbH&Co KG D 35107 Allendorf Tel: +49 6452 70 0 Fax: +49 6452 70 27 80 www.viessmann.de Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP , GB Tel: +44 1952 675000...