Viessmann VITODENS 300 Service Instructions Manual page 50

Wall mounted gas fired condensing boiler. natural gas and lpg version. 4.2 to 13.0 kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
7b:1
*
1
Send time via LON
7F:1
*
1
Detached house
80:1
With a 5 second time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
81:1
Automatic summer/win-
ter time changeover
82:0
Operation with natural
gas
88 :0
Temperature displayed
in Celsius
8A:175
Never adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
*1
Only for weather-compensated control units.
50
Possible change
7b:0
Do not send time via LON
7F:0
Apartment block
Separate adjustment for
holiday program and time
program for DHW heat-
ing, as option
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
time changeover
81:2
The radio clock module
will be recognised auto-
matically
81:3
Accept time via LON
82:1
Operation with LPG (only
adjustable if coding ad-
dress 11:9 has been set;
see page 91)
88 :1
Temperature display in
Fahrenheit
90:0
Fast (low values) or slow
to
(high values) matching of
90:199
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min.