Viessmann VITODENS 300 Service Instructions Manual page 48

Wall mounted gas fired condensing boiler. natural gas and lpg version. 4.2 to 13.0 kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
Domestic hot water
56:0
DHW temperature ad-
justable from 10 to
60 °C
58:0
Without auxiliary func-
tion for DHW heating
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
5b:0
DHW cylinder directly
connected to the boiler
60:20
*
1
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than set DHW
temperature
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
*
2
Without auxiliary
function for DHW heat-
ing
65:...
Information regarding
the type of diverter
valve (not adjustable)
*1
Only for weather-compensated control units.
*2
Only for constant temperature control units.
48
Possible change
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C.
Observe the max. per-
missible DHW tempera-
ture
58:10
Input of a second set
to
DHW value; adjustable
58:60
from 10 to 60 °C
59:1
Starting point adjustable
to
from 1-10 K below the set
59:10
value
5b:1
DHW cylinder connected
downstream of the low
loss header
60:5
The difference between
to
the boiler water tempera-
60:25
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary functions: 1 x
daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos