Viessmann VITODENS 300 Service Instructions Manual page 60

Wall mounted gas fired condensing boiler. natural gas and lpg version. 4.2 to 13.0 kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
F8: 5
For the operation in re-
duced room tempera-
ture mode, the set room
temperature will be
raised (up to the tem-
perature limit set by
coding address F9) to a
value subject to the out-
side temperature, if the
outside temperature
falls below -5 °C.
Observe the setting of
coding address A3.
F9: 14
Below an outside tem-
perature of -14 °C, the
set room temperature
will be raised to the
value selected as set
room temperature, if the
system operates with
the standard room tem-
perature.
FA:20
Raising the set flow
temperature for the
transition from reduced
temperature to standard
room temperature mode
= 20%
Fb:30
Duration for raising the
set flow temperature
(see coding address
FA): 60 min
60
Possible change
F8:+10
Limit for raising the tem-
to
perature in reduced
F8: 60
mode adjustable from
+10 to -60 °C
F8: 61
Function disabled
F9:+10
Limit for raising the set
to
room temperature to the
F9: 60
value selected for stan-
dard mode adjustable
from +10 to -60 °C
FA:0
Raising the set flow tem-
to
perature for the transition
FA:50
from reduced room tem-
perature mode to stan-
dard room temperature
mode, adjustable from 0
to 50%
Fb:0
Duration for raising the
to
set flow temperature ad-
Fb:150
justable from 0 to 150
(corresponds to 0 to 300
min)