Viessmann VITODENS 300 Service Instructions Manual page 78

Wall mounted gas fired condensing boiler. natural gas and lpg version. 4.2 to 13.0 kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
bF
X
C2
X
X
C5
X
X
C6
X
C7
X
X
Cd
X
X
78
System char-
Cause
acteristics
Control mode
Incorrect
LON com-
munication
module
Control mode
Communica-
tion fault -
solar control
unit
Control mode,
Communica-
max. pump
tion error
speed
variable
speed inter-
nal pump
Control mode,
Communica-
max. pump
tion fault -
speed
variable
speed circu-
lation pump,
heating
circuit M2
Control mode,
Communica-
max. pump
tion fault -
speed
external vari-
able speed
circulation
pump, heat-
ing circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Remedy
Replace the LON
communication
module.
Check connec-
tions and coding
address "54".
Check coding ad-
dress "30" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: OFF
(delivered condi-
tion)
Switch 2: OFF
(delivered condi-
tion)
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: OFF
Switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: ON
Switch 2: OFF
Check connec-
tions and the
Vitocom 100.