Viessmann VITODENS 300 Service Instructions Manual page 79

Wall mounted gas fired condensing boiler. natural gas and lpg version. 4.2 to 13.0 kw
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
CE
X
X
CF
X
dA
X
db
X
dd
X
dE
X
E4
X
X
System char-
Cause
acteristics
Control mode
Communica-
tion fault
ext. exten-
sion
Control mode
Communica-
tion fault -
LON com-
munication
module
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
shorted out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
M2 shorted
out
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
lead broken
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit
M2 lead bro-
ken
Burner
Internal fault
blocked
Troubleshooting
Remedy
Check connec-
tions and settings
of coding address
"2E".
Replace the LON
communication
module.
Check the room
temperature sen-
sor
heating cir-
cuit A1.
Check the room
temperature sen-
sor
heating cir-
cuit M2.
Check the room
temperature sen-
sor
heating cir-
cuit A1.
Check the room
temperature sen-
sor
heating cir-
cuit M2.
Replace the con-
trol unit.
79