3/64 | F-B90 Description Fire dampers represent passive fire protection and are designed to utilize compartmentalization to prevent the spread of toxic gases, smoke and fire. The opening and closure of the damper blade can be activated remotely for actuator versions.
Page 4
4/64 | F-B90 • 01, 02 – with grille on one side only. • 11, 22 – with grille on both sides. Types of Activation • H0 Fire damper with a manual crank activation mechanism and with a spring return release mechanism activated by a fusible thermal link set to 74°C.
Page 5
5/64 | F-B90 Product Parts F-B90-... Legend P1 - Damper casing P2 - Damper blade P3 - Actuator P4 - Thermoelectric tripping device (with test button) P5 - Sheet metal grille P6 - Threaded inserts for duct connection P7 - Threaded inserts for the grille P8 - Mechanism cover P9 - Product label P10 - Smoke sensor ORS 144 K (Hekatron)
6/64 | F-B90 Technical Parameters Durability Test • Test procedure with 50 cycles and manual control • No change of the necessary properties. (rotation from 0° to 90°) • Test procedure with 10000 cycles and actuator control • No change of the necessary properties. (rotation from 0°...
Page 7
Make sure that the damper blade is in the closed position during transportation and protected from weather disruptions. The storage of the damper must be indoors. Assessed Performance 19 CE 1396 Systemair Production a.s. Hlavná 371, 900 43 Kalinkovo, Slovakia 1396-CPR-0177 F-B90...
8/64 | F-B90 Diagrams The pressure drop, and A-weighted total discharged sound power level depend on the nominal width and height of the damper and air flow volume at different duct pressures. The type of activation does not influence the airflow parameter, therefore only one activation type is shown in the diagrams.
Page 9
9/64 | F-B90 Diagrams for Supply Air, Grille Type: 00 F-B90-...-00 F-B90-...-00 Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 1000 2000 W: 200, H: 250 W: 200, H: 500 W: 600, H: 500 W: 600, H: 250 W: 400, H: 500...
Page 10
10/64 | F-B90 Diagrams for Extract Air, Grille Types: 01 & 02 F-B90-...-01 F-B90-...-01 Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 2000 W: 200, H: 500 W: 600, H: 500 W: 200, H: 250 W: 400, H: 250 W: 600, H: 250 W: 400, H: 500...
Page 11
11/64 | F-B90 Diagrams for Supply Air, Grille Types: 01 & 02 F-B90-...-01 F-B90-...-01 Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 1000 2000 W: 200, H: 250 W: 600, H: 250 W: 600, H: 500 W: 200, H: 500 W: 400, H: 500...
Page 12
12/64 | F-B90 Diagrams for Extract Air, Grille Types: 11 & 22 F-B90-...-11 F-B90-...-11 Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 W: 600, H: 250 W: 200, H: 500 W: 200, H: 250 W: 600, H: 500 W: 400, H: 250...
Page 13
13/64 | F-B90 Diagrams for Supply Air, Grille Types: 11 & 22 F-B90-...-11 F-B90-...-11 Pressure drop & A-weighted sound power level in dB(A) Pressure drop & A-weighted sound power level in dB(A) 1000 1000 2000 W: 600, H: 500 W: 600, H: 250 W: 200, H: 500 W: 200, H: 250 W: 400, H: 500...
18/64 | F-B90 Ordering Codes W - Width Dimension 150 mm, 175 mm, 200 mm, 225 mm, 250 mm, 280 mm, 300 mm, 315 mm, 350 mm, 355 mm, 400 mm, 450 mm, 500 mm, 550 mm, 560 mm, 600 mm, 630 mm, 650 mm, 700 mm, 710 mm, 750 mm, 800 mm. H - Height Dimensions 250 mm, 375 mm, 500 mm, 625 mm, 750 mm, 875 mm, 1000 mm.
Page 19
19/64 | F-B90 Example of the Ordering Code F-B90-315×375-00-B230T Multiblade fire damper with width of 315 mm and height of 375 mm, without a grille. Activated by a 230 V Belimo actuator.
• Clean the damper from the debris and excess material from the filling or insulation. • Perform damper's functionality check (see "Operation Manual" section). • Connect the continuous duct or mount the removed grille. • Create and/or fill out the Operating Journal included with the damper (Operating Journal can be also downloaded at design.systemair.com)
Page 24
24/64 | F-B90 Legend for Product Handling 1 - Fire damper F-B90 2 - Connected sheet metal ductwork tested according to EN 1366-8 or EN 1366-9 3 - Filling 5 - Grille 8 - Support - brick, metal delivery or wood stud (not part of damper) Fx - Filling per chosen installation F3 - Self-tapping screw size 4,2 ...
25/64 | F-B90 Installation Methods Warning • Obey the applicable regulations and standards of the country that this product will be installed in. • Make sure that only approved/trained personnel performs the installation. • Obey the written instructions and the illustrations in selected installation method. F-B90 EI 60 (v i ↔...
Page 26
26/64 | F-B90 Installation Rules • The duct connected to the fire damper must be supported or hung in such a way that the damper does not carry its weight. The damper must not support any part of the surrounding construction or wall which could cause damage and consequent damper failure.
Page 27
27/64 | F-B90 Installation 1. Wet Procedure to Fill with Plaster, Mortar, or Concrete 1. Prepare the opening in the Wall: NOTE: The dimensions of the openings are the result of the nominal dimensions of the damper with added clearance. The dimensions of the opening will be W1 and H1.
Page 28
28/64 | F-B90 Types 00, 01, 02 Installed in the Wall - Max Resistivity: EI90S 12,5 ≥50 (mm) (mm) >125 >125 >12,5 >50 (mm) (mm)
Page 33
33/64 | F-B90 Wall and/or Ceiling Opening Preparation and Minimum Distances ≥125 mm ≥75 ≥200 ≥12,5 mm (EI60S, EI90S) ≥75 mm (EI60S, EI90S) ≥40 mm; ≥80 kg/m (EI60S, EI90S) (mm) Legend for Installation 1. Wet 1 - Fire damper F-B90 2 - Connected metal ductwork 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall...
Page 34
34/64 | F-B90 Installation 3. Soft Procedure to Fill with Mineral Wool 1. Prepare the opening in the Wall: NOTE: The dimensions of the openings are the result of the nominal dimensions of the damper with added clearance. The dimensions of the opening will be W1 and H1. a.
Page 35
35/64 | F-B90 Types 00, 01, 02 Installed in the Wall - Max Resistivity: EI90S 12,5 ≥50 (mm) (mm) >125 >125 >12,5 >50 (mm) (mm)
Page 40
40/64 | F-B90 Wall and/or Ceiling Opening Preparation and Minimum Distances ≥125 mm ≥75 ≥200 ≥12,5 mm (EI60S, EI90S) ≥75 mm (EI60S, EI90S) ≥40 mm; ≥80 kg/m (EI60S, EI90S) (mm) Legend for Installation 3. SOFT 1 - Fire damper F-B90 2 - Connected metal ductwork 3 - Concrete/masonry/cellular concrete wall or ceiling 4 - Flexible (plasterboard) wall...
Page 41
41/64 | F-B90 Installation 3F. Fit Procedure to Install the Damper with No Gap and Fill with Mineral Wool 1. Prepare the opening in the Wall: NOTE: The dimensions of the openings are the result of the nominal dimensions of the damper with added clearance. The dimensions of the opening will be W1 and H1.
Page 42
42/64 | F-B90 Types 00, 01, 02 Installed in the Wall - Max Resistivity: EI90S 12,5 ≥50 (mm) >125 >12,5 >50 (mm)
46/64 | F-B90 Electrical connections WARNING • Risk of electric shock. • Stop the power supply before you do work on electrical equipment. • Only approved electricians can do work on the electrical system. To access the electrical parts of this product follow instructions in "Product Handling" section. Electrical parameters for type of activation and actuator F-B90 (B230T …...
Page 47
47/64 | F-B90 F-B90 (G230T … GSD24T) W (mm) T | NVF | PC | A 150 175 200 225 250 280 300 315 350 355 400 450 500 550 560 600 630 650 700 710 750 800 G230T | AC 230 V, 50/60 Hz | 9,5 VA | 340TA-230-05 ... G24T | AC (50/60 Hz)/DC 24 V | 9 VA | 340TA-024-05 ...
Page 49
49/64 | F-B90 Type of activation H0 This type of activation mechanism does not have any electrical equipment. Type of activation H2 IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Allow only qualified electricians to work on the electrical system. Microswitch:Power Supply: AC 125/250 V or DC 12/24 V Electric Parameters: 3A NOTES:...
Page 50
50/64 | F-B90 Type of Activation B230T Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: • Caution! Main power supply voltage! •...
Page 51
51/64 | F-B90 Type of Activation B24T IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 52
52/64 | F-B90 Type of Activation BST0 IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: Connection scheme for standardly fitted BKN230-24.
Page 53
53/64 | F-B90 Type of Activation B24T-SR IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 54
54/64 | F-B90 Type of Activation G230T IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 55
55/64 | F-B90 Type of Activation G24T IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 56
56/64 | F-B90 Type of Activation GST0 IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 57
57/64 | F-B90 Type of Activation G24T-SR IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 58
58/64 | F-B90 Type of Activation BSD230T and GSD230T IMPORTANT: Danger of electric shock!Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
Page 59
59/64 | F-B90 Type of Activation BSD24T and GSD24T IMPORTANT: Danger of electric shock! Switch off the power supply before working on any electrical equipment. Only qualified electricians are allowed to work on the electrical system. Power consumption must be observed. NOTES: •...
60/64 | F-B90 Operation Manual Functionality Check Before and after you install the damper, make sure that the dampers functionality is checked. The functionality is checked by: 1. Opening the damper: • Remove the Grille (if fitted) and remove the mechanism housing doors by unscrewing bottom and top door screws. Manual crank activation mechanism: •...
Page 62
62/64 | F-B90 Damper Inspection CAUTION: Never perform inspection when there is air flowing in the duct connected to the damper. Do not change the dampers or their structure without the approval of the manufacturer. The actuator keeps the dampers on stand-by during their life cycle. The operator obeys the applicable regulations and standards to do regular checks of the dampers.
Page 63
63/64 | F-B90 Supplement If you find differences from the terms and the technical specifications that are in this manual, speak to the manufacturer. We reserve the right to make changes to the product without notice.