Troubleshooting; Miscellaneous Leakage; Insufficient Flow; Excessive Foaming - lancer DELTA III PRE-MIX Installation And Service Manual

Counter electric dispenser
Table of Contents

Advertisement

https://appliancetechmanuals.com

4. TROUBLESHOOTING

TROUBLE
4.1

Miscellaneous leakage.

4.2

Insufficient flow.

4.3

Excessive foaming.

4.4
Compressor does not
start (no hum), but
condenser fan motor
runs.
4.5
Compressor starts and
continues to run until
freeze up and will not
cut off.
4.6
Compressor does not
start but hums.
4.7
Compressor starts but
does not switch off start
winding (will run for only B. Incorrect wiring.
a few seconds before
internal overload
switches compressor
off).
4.8
Compressor starts and
runs a short time but
shuts off on overload.
(continued next page)
CAUSE
A. Gap between parts.
B. Damaged or improperly
installed o-rings.
A. Insufficient incoming supply
pressure.
A. Incoming product
temperature too high.
B. Flow rate too high.
C. Air in lines.
D. Poor quality ice.
E. High beverage temperature.
A. Compressor relay or overload
malfunctioning.
B. Inadequate voltage.
C. Incorrect wiring.
D. Compressor malfunctioning.
A. Ice bank control failure.
B. Incorrect wiring.
A. Inadequate voltage.
B. Incorrect wiring.
C. Starting relay malfunctioning.
D. Compressor malfunctioning.
A. Inadequate voltage.
C. Starting relay malfunctioning.
A. Dirty condenser.
B. Insufficient or blocked air flow. B. Remove all obstructions and allow
C. Inadequate voltage.
D. Incorrect wiring.
E. Defective condenser fan motor. E. Replace condenser fan motor.
F. Refrigerant leak.
G. Compressor malfunctioning.
4
REMEDY
A. Tighten appropriately.
B. Replace or adjust appropriate
o-rings.
A. Verify incoming supply pressure
is correct.
A. Correct prior to dispenser.
Consider larger dispenser or
pre-cooler.
B. Readjust.
C. Bleed air from lines.
D. Check quality of ice used in drink.
E. Check refrigeration system.
A. Replace compressor relay or
overload.
B. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
C. Refer to wiring diagram and correct.
D. Replace compressor.
A. Replace ice bank control.
B. Refer to wiring diagram and correct.
A. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
B. Refer to wiring diagram and correct.
C. Replace starting relay. Be sure to
use correct relay. Failure to use
correct relay will cause compressor
failure.
D. Replace compressor.
A. Measure voltage across common
and run terminal on compressor.
B. Refer to wiring diagram and correct.
C. Replace starting relay. Be sure to
use correct relay. Failure to use
correct relay will cause compressor
failure.
A. Clean the condenser.
for minimum clearance of
15 inches (38.1 cm) over top.
C. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
D. Refer to wiring diagram and correct.
F. Repair and recharge.
G. Replace compressor.