Technical Data

4.1 General

4.1
General
Current Input
Recommended permanent operating
temperature
Limiting temporary (transient) operating
temperature
Limit temperatures during transport
4.2

Rated electrical parameters

Rated auxiliary direct voltage:
Tolerance
Alternating Voltage
Rated current
Rated frequency
Overload capability::
Current overload capability
Voltage path overload capacity
Power consumption:
Current
Voltage
Power Consumption:
4.3

Functional Data

4.3.1

ATS

Time Tolerance of ATS
Frequency Tolerance
Voltage Tolerance
Current Tolerance
Frequency Range
External BI filter time
96
-5~55
-20~70°C
-25~70°C
220V,110V
+20%,-20%
80~125/3V(Un)
5 A,1 A (In)
50Hz,60Hz
4 IN continuous
30 IN for 10 s
100 IN for 1 s
230 V continuous
Approx. 0.3 VA(In=5 A)
Approx. 0.05 VA(In=1 A)
Approx. 0.10 VA/Phase
Quiescent, Approx. 8 W
Energized, Approx. 15 W
< 50ms
<0.02Hz
<0.2V
<0.01In
0Hz ~ 66Hz
10ms
C53000-G1176-C368-1, Release Date 07.2012