Table 3-9
Binary inputs
BI8
BI9
BI10
BI11
BI12
BI13
BI14
BI15
1)
Factory settings for devices with rated power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115/230 VAC
3)
Use only with control voltages 220 to 250 VDC
Jumpers X71, X72 and X73 on the input/output module C-I/O-1 are used to set the bus address and must not
be changed. The following table lists the jumper presetting.
Mounting locations of modules are shown in Figures 3-2.
Table 3-10
Jumper
X71
X72
X73
Jumpers X71, X72 and X73 on the input/output board C-I/O-10 are used to set the bus address and must not
be changed. The following Table lists the jumper presettings.
Table 3-11
Jumper
X71
X72
X73
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
Jumper setting of pickup voltages of binary inputs BI8 to BI15 on Input/Output module module
C- I/O-1 in the 7VU681
Jumper
17 VDC Threshold
X21/X22
X23/X24
X25/X26
X27/X28
X29/X30
X31/X32
X33/X34
X35/X36
Module address jumper setting of input/output module C-I/O-1 for 7VU681
Presetting
2-3(L)
2-3(L)
1-2(H)
Jumper settings of PCB Address of the input/output board C-I/O-10
Presetting
2-3(L)
2-3(L)
1-2(H)
1)
73 VDC Threshold
2)
L
M
L
M
L
M
L
M
L
M
L
M
L
M
L
M
Mounting And Commissioning
3.1 Mounting And Connections
3)
154 VDC Threshold
H
H
H
H
H
H
H
H
69