Information List - Siemens SIPROTEC 7VU681 User Manual

Multifunction automatic transfer system
Table of Contents

Advertisement

Addr.
A Setting Group->ATS
0231
8938
8939
8929
8919
8920
8921
8922
8923
8924
8925
8926
A Setting Group->Load Shedding
8940
8941
8942
8943
2.1.8

Information List

Addr.
17748
17759
17680
17681
17682
18013
18001
18002
17749
17788
17683
17693
17703
17713
17798
17910
17750
17789
17684
17694
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
Parameter
Manually Restart ATS
Time Delay to Ready Status
Time Delay to Un-Ready Status
Time Delay to Switch CB
Transfer Line1->Line2 Time Delay 0.05<=..<=600.00
Transfer Line2->Line1 Time Delay 0.05<=..<=600.00
Transfer Bus1->Bus2 Time Delay
Transfer Bus2->Bus1 Time Delay
Transfer Transformer1->Tran.2
Time Delay
Transfer Transformer2->Tran.1
Time Delay
Busbar Load-Shifting Time Delay
Transformer Energization Time
Load-Shedding Active Time
Load-Shedding Current Threshold 0.02<=..<=5.00,oo 1.00I/In
Load-Shedding Time Delay 1
Load-Shedding Time Delay 2
Information
>BLOCK ATS
>Manually Restart
ATS is Active
ATS switched OFF
ATS is Blocked
ATS is Ready
ATS Succeeded
ATS Failed
>BLOCK Line1 -> Line2
Line1 -> Line2 is Blocked
Line1 -> Line2 is Active
Line1 -> Line2 is Ready
Line1 -> Line2 Initiated
Line1 -> Line2 Pickup
Line1 -> Line2 Succeeded
Line1 -> Line2 Failed
>BLOCK Line2 -> Line1
Line2 -> Line1 is Blocked
Line2 -> Line1 is Active
Line2 -> Line1 is Ready
Setting Options
Default Setting Comments
Yes
No
No
..
0.05<=
<=600.00
10sec
..
0.01<=
<=600.00
10sec
0.05<=..<=600.00,
0.04sec
0
0.50sec
0.50sec
0.05<=..<=600.00
0.50sec
0.05<=..<=600.00
0.50sec
0.05<=..<=600.00
0.50sec
0.05<=..<=600.00
0.50sec
0.05<=..<=600.00
5sec
0.05<=..<=600.00
0.50sec
0.1<=..<=60000.00 100.0sec
0.1<=..<=600.00
10.00sec
0.1<=..<=600.00
20.00sec
Type
Function No.
SP
SP
OUT
OUT
OUT
OUT
200
OUT
OUT
SP
OUT
OUT
OUT
OUT
OUT
OUT
200
OUT
200
SP
OUT
OUT
OUT
Function
2.1 ATS