Siemens SIPROTEC 7VU681 User Manual page 66

Multifunction automatic transfer system
Table of Contents

Advertisement

Mounting And Commissioning
3.1 Mounting And Connections
Table 3-3
Jumper
X40
Table 3-4
Binary inputs
BI1
BI2
BI3
BI4
BI5
1)
Factory settings for devices with rated power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115/230 VAC
3)
Use only with pickup voltages 220 or 250 VDC
The R485 interface can be converted into an RS232 interface by modifying the jumpers.
Jumpers X105 to X110 must be set to the same position !
Table 3-5
Jumper
X103 to X104
X105 to X110
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the
modem.
Table 3-6
Jumper
X111
1)
Default setting of releases 7VU68.../BB
Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC? 4 devices is always operated in the
half-duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2:This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend use
of a standard RS232 modem connection cable (converter 9-pole on 25-pole).
66
Jumper position of the quiescent state of the Life contact on the C-CPU-2 processor module
Open in the quiescent
state
(NO contact)
1-2
Jumper setting of the control voltages of binary inputs BI1 to BI5 on the C-CPU-2 processor
module
Jumper
X21
X22
X23
X24
X25
Jumper Settings of the Integrated RS232/RS485 Interface on the C-CPU-2 Board
/CTS from interface RS232
Jumper setting for CTS (flow control) on the C-CPU-2 processor module
/CTS from interface RS232
Nominal Voltage
Closed in the quiescent
state
(NC contact)
2-3
1)
17 V Threshold
1-2
1-2
1-2
1-2
1-2
1-2
1-2
1-2
C53000-G1176-C368-1, Release Date 07.2012
Presetting
2-3
2)
73V Threshold
154V Threshold
2-3
2-3
2-3
2-3
2-3
/CTS triggered by /RTS
1-2
2-3
/CTS triggered by /RTS
1)
2-3
SIPROTEC, 7VU681, User Manual
3)
3-4
3-4
3-4
3-4
3-4