When the parameter 9020 Phase O/C for Busbar Energization is set to ON and bus-tie CB is closed, Phase
overcurrent for busbar energization protection will start to run. The running time is set by the parameter
9019A Active Time for Busbar Energization.
2. Compound voltage control can be enabled or disabled by setting the parameter 9021 Compound Voltage
Control to YES or NO.
3. PT broken wire cannot block phase overcurrent for busbar energization protection.
4.
After the trip signal is released, the dropout of the voltage signal cannot reset the trip signal, only current
dropout can reset the trip signal.

2.2.3.1 Settings

Addr.
Protection Functions -> General
9020
9019A
Protection Functions -> Voltage Control
9002
9003
Protection Functions -> Ph. O/C Energiz.
9021
9024
9025
9026
9027

2.2.3.2 Information List

No.
17942
Ph.O/C Ene.ACT.
17943
Ph.O/C Ene. OFF
17944
Ph.O/C Ene. BLK
17928
Ph.O/C-1Ener.PU
17929
Ph.O/C-1Ene.Tr.
17930
Ph.O/C-2Ener.PU
17937
>BLK Ph. O/C En
17983
Ph.O/CEn.ON/OFF
SIPROTEC, 7VU681, User Manual
C53000-G1176-C368-1, Release Date 07.2012
Settings
Phase O/C for Busbar
Energization
Active time for Busbar
Energization
Ph-Ph Undervoltage
Threshold
U2 Overvoltage Threshold
Compound Voltage Control
Phase O/C-1 for Busbar
Energ.
Phase O/C-1 Time Delay for
Busbar Energization
Phase O/C -2 for Busbar
Energization
Phase O/C -2 Time Delay for
Busbar Energ.
Information
OUT
OUT
OUT
OUT
OUT
OUT
SP
IntSP
Setting Options
ON
OFF
OFF
0.01s..600.00s
5.00s
1V..125V, 0V
70V
1V..125V, ∞
8V
Yes
No
No
0.1A..35A
2A
0s..60s, ∞
0.5s
0.1A..35A
4A
0s..60s, ∞
0.1s
Type
Funcion No.
200
200
200
2.2 Protection
Default Setting
Comments
Inf. No.
54
56
87