Download Print this page

Advertisement

Quick Links

7SR157 Argus
Check and System Synchronising Relay
Energy Management
Reyrolle
Protection
Devices

Advertisement

loading

Summary of Contents for Siemens 7SR157 Argus

  • Page 1 Reyrolle Protection Devices 7SR157 Argus Check and System Synchronising Relay Energy Management...
  • Page 3 7SR157 Contents Contents Technical Manual Chapters Description of Operation Settings and Instruments Performance Specification Data Communications Definitions Installation Guide Commissioning and Maintenance Applications Guide...
  • Page 4 7SR157 Contents...
  • Page 5 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 6: Table Of Contents

    6.6 Real Time Clock ..........................37 6.6.1 Time Synchronisation – Data Communication Interface............37 6.6.2 Time Synchronisation – Binary Input .................. 37 6.7 Settings Groups ..........................37 6.8 Password Feature ........................... 38 Chapter 1 - Page 2 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 7 Figure 4-6 Logic Diagram: Close Circuit Supervision Feature (74CCS) .............. 32 List of Tables Table 1-1 7SR157 Ordering Options ......................6 Table 2-1 Summary of 7SR157 Relay Configurations ..................9 Table 4-1 Operating Mode ......................... 36 © 2022 Siemens Protection Devices Limited Chapter 1 - Page 3 of 38...
  • Page 8 The following notational and formatting conventions are used within the remainder of this document:  Setting Menu Location MAIN MENU>SUB-MENU  Setting: Elem name -Setting  Setting value: value  Alternatives: [1st] [2nd] [3rd] Chapter 1 - Page 4 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 9: Section 1: Introduction

    Where external resistors are fitted to relays, these may present a danger of electric shock or burns, if touched. Front Cover The front cover provides additional securing of the relay element within the case. The relay cover should be in place during normal operating conditions. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 5 of 38...
  • Page 10: Table 1-1 7Sr157 Ordering Options

    Protection Function Packages Standard Version - 25 Check Synchronising Additional Functionality No additional functionality Spare E4 case is standard, E6 case is required if IEC61850 option fitted Chapter 1 - Page 6 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 11: Figure 1-1 Protection Functions

    Chapter 1 - 7SR157 Description of Operation The relay has 2 VT inputs: Figure 1-1 Protection Functions © 2022 Siemens Protection Devices Limited Chapter 1 - Page 7 of 38...
  • Page 12: Figure 1-2 Connections Diagram For 7Sr157 Relay

    7SR157 Technical Manual Figure 1-2 Connections Diagram for 7SR157 Relay Chapter 1 - Page 8 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 13: Section 2: Hardware Description

    The relay should only be held by the top and bottom plates and the user should not touch the exposed PCB’s. Figure 2-1 Relay shown withdrawn © 2022 Siemens Protection Devices Limited Chapter 1 - Page 9 of 38...
  • Page 14: Front Cover

    The only ‘action’ that is permitted is to reset the Fault Data display, latched binary outputs and LEDs by using the TEST/RESET button. Chapter 1 - Page 10 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 15: Power Supply Unit (Psu)

    The PSU does not contain any fuses or user serviceable protection components. Typically the PSU is connected to the auxiliary supply via an external HRC fuse rated at 6A (BS88/IEC60259). Isolation links may also be installed in accordance with user requirements. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 11 of 38...
  • Page 16: Operator Interface/ Fascia

    Blank label for user defined information. Figure 2-6 Close up of Relay Label A template is available in Reydisp Evolution software to allow users to create and print customised labels. Chapter 1 - Page 12 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 17: Figure 2-7 Close Up Of Relay Identifier

    The ‘Relay Identifier’ is used in communication with Reydisp to identify the relay. Pressing the Cancel button several times will always return the user to this screen. Figure 2-7 Close up of Relay Identifier © 2022 Siemens Protection Devices Limited Chapter 1 - Page 13 of 38...
  • Page 18 The status of hand reset LEDs is maintained by a back up storage capacitor in the event of an interruption to the d.c. supply voltage. Chapter 1 - Page 14 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 19: Voltage Inputs

    INPUT CONFIG > BINARY INPUT CONFIG menu. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 15 of 38...
  • Page 20: Binary Outputs (Output Relays)

    On loss of the auxiliary supply hand-reset outputs will reset. When the auxiliary supply is re-established the binary output will remain in the reset state unless the initiating condition is still present. Chapter 1 - Page 16 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 21: Virtual Input/Outputs

    Virtual input/outputs can also be used as data items in equations. The status of the virtual inputs and outputs is volatile i.e. not stored during power loss. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 17 of 38...
  • Page 22: Self Monitoring

    A meter, Miscellaneous Meters>Unexpected Restarts, is provided to show how many Unexpected Restarts have occurred during the previous Unexpected Restart Period. This is resettable from the front fascia. Chapter 1 - Page 18 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 23: Protection Healthy/Defective

    If the relay is withdrawn from the case, the case shorting contact will make across the N/C contacts to provide and external alarm. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 19 of 38...
  • Page 24: Section 3: Voltage Monitoring Functions

    Although a wide range is provided for live and dead voltage detector elements, the user must ensure that the live and dead zones do not overlap. Figure 3-1 VT Level Mode: 2 State Chapter 1 - Page 20 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 25: Vt Level Mode: 3 State

    This mode applies a 3% hysteresis setting to the drop off on both thresholds, to minimise ‘chattering’ of the element with frequency excursion. Figure 3-2 VT Level Mode: 3 State Live Output Figure 3-3 VT Level Mode: 3 State Dead Output © 2022 Siemens Protection Devices Limited Chapter 1 - Page 21 of 38...
  • Page 26: Undervoltage Detector

    0.1V. Each also has an independent Voltage Trim Angle in the range of -45° to + 45° with a step size of 0.1°. Chapter 1 - Page 22 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 27: Section 4: Control Functions

    25 Check Sync Angle setting value. Whilst within the limits the phase angle can be increasing or decreasing and the element will still issue a valid close signal. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 23 of 38...
  • Page 28: Close Guard

    Check synchronizing conditions were not met; a Close Guard output is set. Close Guard alert is by default set to General Alarm 7 with the message ‘Close Guard Active’, which is also displayed on the relay LCD. Chapter 1 - Page 24 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 29: System Split Detector

    Slip: The frequency difference between the Line and Bus Voltages at which a system Split is detected is set by changing the 25 Split Slip in the CHECK SYNC MENU. The setting range is from 0 to 2Hz° (setting step is 0.01Hz). © 2022 Siemens Protection Devices Limited Chapter 1 - Page 25 of 38...
  • Page 30: System Sync

    (This ensures that a close output will not be given if there is a transient disturbance on the system due to e.g. some remote switching operations). Figure 4-3 illustrates the System Sync Function logic. Chapter 1 - Page 26 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 31: Figure 4-3 System Sync Function Logic

    Chapter 1 - 7SR157 Description of Operation Figure 4-3 System Sync Function logic © 2022 Siemens Protection Devices Limited Chapter 1 - Page 27 of 38...
  • Page 32: Close On Zero

    InSyncCOZ or COZ In Progress outputs from being set. Figure 4-4 illustrates the Cloze on Zero Function logic. Figure 4-4 Close On Zero Function logic Chapter 1 - Page 28 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 33: Synchronising Bypass

    Alarms can be generated from the following outputs: LLLB (Live Line and Live Bus) DLDB (Dead Line and Dead Bus) LLDB (Live Line and Dead Bus) DLLB (Dead Line and Live Bus) © 2022 Siemens Protection Devices Limited Chapter 1 - Page 29 of 38...
  • Page 34: Quick Logic

    En Counter Reset Mode = Multi Shot: The En Counter Reset Time is started each time the counter is incremented. Where En Counter Reset Time elapses without further count increments the count value is reset to zero. Chapter 1 - Page 30 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 35: Figure 4-5 Sequence Diagram: Quick Logic Pu/Do Timers (Counter Reset Mode Off)

    Protection functions can be used in Quick Logic by mapping them to a Virtual Input / Output. Refer to Chapter 7 – Applications Guide for examples of Logic schemes. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 31 of 38...
  • Page 36: Section 5: Supervision Functions

    The use of one or two binary inputs mapped to the same Trip Circuit Supervision element allows the user to realise several alternative monitoring schemes. Figure 4-6 Logic Diagram: Close Circuit Supervision Feature (74CCS) Chapter 1 - Page 32 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 37: Section 6: Other Features

    For further details refer to the following publications: Model Implementation Conformance Statement (MICS) Protocol Implementation Conformance Statement (PICS) Protocol Implementation Extra Information for Testing (PIXIT) © 2022 Siemens Protection Devices Limited Chapter 1 - Page 33 of 38...
  • Page 38: Data Storage

    The user will then have to press the TEST/RESET► button a further time (four in total) to reset the relay. Chapter 1 - Page 34 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 39: Disk Activity Warning

    The relay will scroll through these meters at an interval set in the System Config/Favourite Meters Timer menu. For a detailed description refer to Technical Manual Chapter 2 – Settings and Instruments. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 35 of 38...
  • Page 40: Operating Mode

    Enabled Enabled Disabled Enabled Enabled Historical Information Waveform Records Enabled Enabled Enabled Event Records Enabled Enabled Enabled Fault Information Enabled Enabled Enabled Setting Information Enabled Enabled Enabled Chapter 1 - Page 36 of 38 © 2022 Siemens Protection Devices Limited...
  • Page 41: Real Time Clock

    (Select Grp Mode: Level triggered) or latches into the selected group after energisation of the input (Select Grp Mode: Edge triggered). Settings are stored in non-volatile memory. © 2022 Siemens Protection Devices Limited Chapter 1 - Page 37 of 38...
  • Page 42: Password Feature

    7SR157 does not provide a Control Menu and therefore this password is not used. The password validation screen also displays a numerical code. If the password is lost or forgotten, this code should be communicated to Siemens Protection Devices Ltd. and the password can be retrieved. Chapter 1 - Page 38 of 38...
  • Page 43 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 44 Figure 2-2 RS485 connection to PC ........................10 Figure 2.1-3 EN100 Ethernet Module ........................11 Figure 2-3 PC Communications Port Selection ...................... 13 Figure 2-4 PC Language File Editor ........................14 Chapter 2 - Page 2 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 45: Section 1: Introduction

    To change the contrast on the LCD insert a flat bladed screwdriver into the screw head below the contrast symbol, turning the screw head left (anti-clockwise) lightens the contrast of the LCD and turning it right (clockwise) darkens the display. Figure 1-2 Fascia Contrast symbol © 2016 Siemens Protection Devices Limited Chapter 2 - Page 3 of 14...
  • Page 46: Operation Guide

    This push-button is used to return the relay display to its initial status or move one level up in the menu structure. Pressed repeatedly will return to the relay identifier screen. It is also used to reject any alterations to a setting while in the edit mode. TEST/RESET Chapter 2 - Page 4 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 47 BINARY OUTPUT CONFIG LED CONFIG PICK UP CONFIG TRIP CONFIG DEMAND / DATA LOG DATA STORAGE WAVEFORM STORAGE FAULT STORAGE COMMUNICATIONS ENERGY STORAGE Figure 1-4 Menu Structure © 2016 Siemens Protection Devices Limited Chapter 2 - Page 5 of 14...
  • Page 48: Setting Mode

    Chapter 2 - Page 6 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 49: Instruments Mode

    Displays the status of voltage blocking elements. L-U/V, B-U/V or Volt-Diff DEMAND METERS This sub-group includes all the meters that are associated with DEMAND. TEST/RESET ► allows access to this sub-group →to view © 2016 Siemens Protection Devices Limited Chapter 2 - Page 7 of 14...
  • Page 50 COM2 Tx displayed. COM2 Rx Error Pressing TEST/RESET ► can reset the meter. COM2 Rx EN100 INFORMATION Displays EN100 information Chapter 2 - Page 8 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 51: Fault Data Mode

    TEST/RESET► button. Each record contains data on the operated elements, analogue values and LED flag states at the time of the fault. The data is viewed by scrolling down using the ▼ button. © 2016 Siemens Protection Devices Limited Chapter 2 - Page 9 of 14...
  • Page 52: Section 2: Setting & Configuring The Relay Using Reydisp Evolution

    Front USB connection To connect your PC locally via the front USB port. Figure 2-1 USB connection to PC 2.1.2 Rear RS485 connection Figure 2-2 RS485 connection to PC Chapter 2 - Page 10 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 53: Optional Rear En100 Ethernet Module (Com3)

    Green LED (Physical Link) Off – No link On – Link present Yellow LED (Activity) Off – No traffic On/flashing - Traffic Figure 2.1-3 EN100 Ethernet Module © 2016 Siemens Protection Devices Limited Chapter 2 - Page 11 of 14...
  • Page 54: Configuring Relay Data Communication

    0, 1 ... 65533, 65534 The address of the master to which unsolicited events will be sent. DNP3 Application Timeout 5, 6 ... 299, 300 Selects the DNP3 application timeout time. Chapter 2 - Page 12 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 55: Connecting To The Relay For Setting Via Reydisp

    Figure 2-4 PC Communications Port Selection The relay settings can now be configured using the Reydisp software. Please refer to the Reydisp Evolution Manual for further guidance. © 2016 Siemens Protection Devices Limited Chapter 2 - Page 13 of 14...
  • Page 56: Configuring The User Texts Using Reydisp Language Editor

    Care should be taken to ensure a unique file name is given including a version control reference. The user will be prompted to restart the relay to activate the language file. Please refer to the Language Editor Manual for further guidance. Chapter 2 - Page 14 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 57 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 58 7SR158 Technical Manual Chapter 3 - Page 2 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 59 Reference .......................... 18 3.1.2 Operate and Reset Time ....................18 3.2 60 VTF VT Failure ........................... 18 3.2.1 Reference .......................... 18 3.2.2 Operate and Reset Time ....................18 © 2022 Siemens Protection Devices Limited Chapter 3 - Page 3 of 18...
  • Page 60: Section 1: Common Functions

    See appropriate case outline and panel drilling drawing, as specified in Diagrams and Parameters of the Installation section, for complete dimensional specifications. 1.1.4 Weights Parameter Value 7SR157, E4 Case 2.7 kg Net weight 7SR157, E6 case 3.65.kg Chapter 3 - Page 4 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 61: Energising Quantities

    0.035 0.035 0.035 0.035 Per LED – Yellow 0.07 0.07 0.07 0.07 0.07 0.07 0.07 Per Binary Output 0.35 0.35 0.35 0.35 Optional IEC 61850 Comms Interface © 2022 Siemens Protection Devices Limited Chapter 3 - Page 5 of 18...
  • Page 62: Ac Analogue Voltage

    1.2.2.1 Burden Attribute Value AC Burden 0.02 VA @ 63.5 V, ≤ 0.06 VA @ 110 Vrms 1.2.2.2 Thermal Withstand Attribute Value Overvoltage Withstand (Continuous) 300 Vrms Chapter 3 - Page 6 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 63: Binary (Digital) Outputs

    For AC operation the BI pick-up delay should be set to 0ms and the drop-off delay to 25ms. For AC operation wiring should be less than 10 metres in length. © 2022 Siemens Protection Devices Limited Chapter 3 - Page 7 of 18...
  • Page 64: Functional Performance

    The specification below applies only while no external synchronisation signal (e.g. 60870-5-103) is being received. Attribute Value  3.5 ppm (no auxiliary supply connected) Accuracy (-10 to +55  100 ppm (auxiliary supply connected) Chapter 3 - Page 8 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 65: Environmental Performance

    Installed with cover on Rear Enclosure (case) IP 20 Front IP 20 Installed with cover removed Rear Enclosure (case) IP 20 Rear wiring terminal access IEC 60255-27:2014 (5.1.5.2.6) IP 10 © 2022 Siemens Protection Devices Limited Chapter 3 - Page 9 of 18...
  • Page 66: Emissions

    Radiated Emissions: Conducted IEC 60255-26 & CISPR 22 Limits Type Quasi-peak Average 0.15 to 0.5 MHz 79 dB(V) 66 dB(V) 0.5 to 30 MHz 73 dB(V) 60 dB(V) Chapter 3 - Page 10 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 67: Immunity

    RV = Residual Voltage Test Value. Two conditions: (a) Range voltage low-20% and (b) Range voltage high +20% No effect on relay performance. Restart with no mal-operation, loss of data or relay damage. © 2022 Siemens Protection Devices Limited Chapter 3 - Page 11 of 18...
  • Page 68 Spot Frequencies 27 MHz & 68 MHz 10 V 1.4.3.8 Magnetic Field with Power Frequency IEC 61000-4-8 Level 5 100A/m, (0.126mT) continuous 50Hz 1000A/m, (1.26mT) for 3s Chapter 3 - Page 12 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 69: Mechanical

    X-plane - 3.5mm displacement below crossover freq (8-9Hz) 1.0gn above  5% Seismic response Y-plane - 1.5mm displacement below crossover freq (8-9Hz) 0.5gn above 1.4.4.4 Mechanical Classification Type Level Durability > 10 operations © 2022 Siemens Protection Devices Limited Chapter 3 - Page 13 of 18...
  • Page 70: Section 2: Control & Logic Functions

    ,  1% V Dead reset level live,act Dead Hysteresis level - 3% V dead,act  1% Repeatability  5% -10°C to +55°C Variation  1% ± 5% Chapter 3 - Page 14 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 71: Line And Bus Undervolts Element

    Operate and Reset Level Attribute Value Operate level ,  2 % V 100% V or ± 0.5 V diff Reset level  V – 3%  2% Repeatability © 2022 Siemens Protection Devices Limited Chapter 3 - Page 15 of 18...
  • Page 72: Check Synchronising

    25 Check Sync Timer Attribute Value  1% or  20ms Accuracy Repeatability  1% or  20ms  5% -10°C to +55°C Variation  5% ± 5 % Chapter 3 - Page 16 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 73: System Synchronising

    25 System Sync Timer Attribute Value Accuracy  1% or  20ms  1% or  20ms Repeatability  5% -10°C to +55°C Variation  5% ± 5% © 2022 Siemens Protection Devices Limited Chapter 3 - Page 17 of 18...
  • Page 74: Section 3: Supervision

    ,  1 % or  20ms Operate time following delay basic  1% or 20ms Repeatability  5% -10°C to +55°C Variation  5% ± 5% Chapter 3 - Page 18 of 18 © 2022 Siemens Protection Devices Limited...
  • Page 75 No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 76 7SR157 Technical Manual Chapter 4 - Page 2 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 77 5.3.3 Binary Output Status Points and Control Relay Output Blocks..........41 5.3.4 Counters............................ 44 5.3.5 Analog Inputs..........................45 5.4 Additional Settings........................... 46 6. Not Applicable......................47 7. IEC61850 Protocol Support..................49 7.1 Introduction...............................49 8. Serial Modems......................51 © 2016 Siemens Protection Devices Limited Chapter 4 - Page 3 of 58...
  • Page 78 List of Figures Fig. 2-1 Communication to Front USB Port........................8 Fig. 2-2 Communication to Multiple Devices using RS485 (Standard Port)............. 10 Fig. A1 Operating Mode Table..........................57 Chapter 4 - Page 4 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 79 Reydisp Evolution or Reydisp Manager Software is available, for computers running Microsoft Windows™, to connect to devices to provide operational information, post-fault analysis, setting interrogation and editing facilities etc. Configuration software can be downloaded from our website http://www.siemens.com/energy. This section specifies connection details and lists the information available through the individual protocols.
  • Page 80 7SR157 Technical Manual Chapter 4 - Page 6 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 81: Introduction

    IEC 60870-5-103 protocol connection to Reydisp. Any port not required can be disabled by setting its protocol to OFF. When connecting to Reydisp Evolution software the protocol for the relevant port should be set to IEC60870-5-103. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 7 of 58...
  • Page 82: Usb Interface (Com2)

    The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable RS485 120 Ohm screened twisted pair cable. Chapter 4 - Page 8 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 83 EVEN accordance with the master device. Local Refer to Appendix COM1-RS485 Remote 1, page 57, for Local or Remote Mode further explanation Remote © 2016 Siemens Protection Devices Limited Chapter 4 - Page 9 of 58...
  • Page 84 System station available To Control System RS 485 Twisted pair Cable RS485 RS485 RS485 Bus Termination Polarity Fig. 2-2 Communication to Multiple Devices using RS485 (Standard Port) Chapter 4 - Page 10 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 85: Iec 60870-5-103 Definitions

    The Station Address of the port being used must be set to a suitable address within the range 0 - 254 to enable communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 11 of 58...
  • Page 86: Cause Of Transmission

    Negative command acknowledge Note: Events listing a GI cause of transmission can be raised and cleared; other events are raised only. Chapter 4 - Page 12 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 87: Application Service Data Unit (Asdu) Type

    2 Time tagged message (relative time) (monitor direction) 3.1 Measurands I 4 Time-tagged measurands with relative time 5 Identification message 6 Time synchronisation 7 General Interrogation Initialization 9 Measurands II 20 General command © 2016 Siemens Protection Devices Limited Chapter 4 - Page 13 of 58...
  • Page 88: Point List

    5 Binary Input 5 1 SE, GI 6 Binary Input 6 1 SE, GI 1 Virtual Input 1 1 SE, GI 2 Virtual Input 2 1 SE, GI Chapter 4 - Page 14 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 89 5 SE 5 Power On 1 SE, GI 1 SE 19 LED Reset 20 Ack, Nak 22 Settings changed 1 SE 1 SE, GI 23 Setting G1 selected © 2016 Siemens Protection Devices Limited Chapter 4 - Page 15 of 58...
  • Page 90 154 User SP Command 5 20 Ack, Nak 1 SE, GI 155 User SP Command 6 20 Ack, Nak 1 SE, GI 156 User SP Command 7 Chapter 4 - Page 16 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 91: Measurands

    Measured Diff (1.2x) (Window 0%) Slip 3.4.3 Disturbance Recorder Actual Channel (ACC) Numbers The following Disturbance Recorder channel numbers apply to this device. Description 12 VLine 13 VBus © 2016 Siemens Protection Devices Limited Chapter 4 - Page 17 of 58...
  • Page 92 7SR157 Technical Manual Chapter 4 - Page 18 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 93: Modbus Definitions

    Communication via MODBUS over Ethernet requires external devices. Please refer to the documents TCPIP Catalogue Sheet and TCPIP Interface Technical Guidance Notes for more information. Definitions with shaded area are not available on all relay models. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 19 of 58...
  • Page 94: Modbus Register Data Types

    1,000,000 as a float (from above) we have 49742400h. Assume this is stored in the registers 30001 and 30002, it would look as follows. Address Value 30001 4974 Chapter 4 - Page 20 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 95: Fp_32Bits_3Dp

    5678 we have 162Eh. Assume this is stored in the register 30001, it would look as follows: Address Value 30001 162E On reception this register should be interpreted as a 16 bit integer. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 21 of 58...
  • Page 96: Event

    Measurand format R32.23, sent least significant byte first. The following tables show the fields in the different event records as they are returned. Byte Content FUN INF ms L Event Type 1 Format. Chapter 4 - Page 22 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 97: Eventcount

    Most Significant Bit (MSB). Bit values can only be zero or one. Any unused bits will be set to zero. BITSTRING & MODBUS © 2016 Siemens Protection Devices Limited Chapter 4 - Page 23 of 58...
  • Page 98 0905h. Assume this is stored in the register 30001, it would look as follows: Address Value 30001 0905 On reception this register should be interpreted as a 16 bit integer. Chapter 4 - Page 24 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 99: Point List

    00215 User DP Command 8 4.3.2 Inputs (Read Only Binary values) Address Description 10001 Binary Input 1 10002 Binary Input 2 10003 Binary Input 3 10004 Binary Input 4 © 2016 Siemens Protection Devices Limited Chapter 4 - Page 25 of 58...
  • Page 100 10504 Virtual Input 4 10505 Virtual Input 5 10506 Virtual Input 6 10507 Virtual Input 7 10508 Virtual Input 8 10601 LED 1 10602 LED 2 10603 LED 3 Chapter 4 - Page 26 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 101: Input Registers (Read Only Registers)

    30060 Frequency FP_32BITS_3DP 1.000000 Frequency Hz 30167 Fault Records UINT16 1.000000 Fault Records 30168 Event Records UINT16 1.000000 Event Records 30169 Waveform Records UINT16 1.000000 Waveform Records © 2016 Siemens Protection Devices Limited Chapter 4 - Page 27 of 58...
  • Page 102: Holding Registers (Read Write Registers)

    BITSTRING 0.000000 Equation 17-32 status 40368 Active Setting Group UINT16 1.000000 Active Setting Group 40401 Event Count EVENTCOUNT 0.000000 Events Counter 40402 Event EVENT 0.000000 8 Registers Chapter 4 - Page 28 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 103: Dnp3 Definitions

    (Also see the DNP 3.0 Implementation Table in Section 5.2, beginning on page 32). Vendor Name: Siemens Protection Devices Ltd. Device Name: 7SR157, using the Triangle MicroWorks, Inc. DNP3 Slave Source Code Library, Version 3. Device Function: Highest DNP Level Supported:...
  • Page 104 Configurable 16 Bits Default Object 32 Bits Default Variation: _____ Other Value: _____ Point-by-point list attached Point-by-point list attached Sends Multi-Fragment Responses: Configurable Sequential File Transfer Support: Chapter 4 - Page 30 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 105 Append File Mode Custom Status Code Strings Permissions Field File Events Assigned to Class File Events Send Immediately Multiple Blocks in a Fragment Max Number of Files Open © 2016 Siemens Protection Devices Limited Chapter 4 - Page 31 of 58...
  • Page 106: Implementation Table

    (unsol. resp) 00, 01 (start-stop) Binary Output 1 (read) 06 (no range, or all) - Any Variation 22 (assign class) 07, 08 (limited qty) 17, 27, 28 (index) Chapter 4 - Page 32 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 107 06 (no range, or all) 1 (read) 17, 28 (index see note 1) (without Flag) 07, 08 (limited qty) (response) - see note 2) 17, 27, 28 (index) © 2016 Siemens Protection Devices Limited Chapter 4 - Page 33 of 58...
  • Page 108 07, 08 (limited qty) (unsol. resp) 16-Bit Counter Change 06 (no range, or all) 1 (read) (response) 17, 28 (index) Event (with Time) 07, 08 (limited qty) Chapter 4 - Page 34 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 109 32-Bit Frozen Analog Input (with Time of freeze) 16-Bit Frozen Analog Input (with Time of freeze) 32-Bit Frozen Analog Input (without Flag) 16-Bit Frozen Analog Input (without Flag) © 2016 Siemens Protection Devices Limited Chapter 4 - Page 35 of 58...
  • Page 110 00, 01 (start-stop) Short Floating Point 1 (read) 06 (no range, or all) 17, 28 (index Analog Input Deadband (response) 07, 08 (limited qty) - see note 2) Chapter 4 - Page 36 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 111 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.) Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7). © 2016 Siemens Protection Devices Limited Chapter 4 - Page 37 of 58...
  • Page 112: Point List

    208 Close Circuit Fail 2 209 Close Circuit Fail 3 210 Close Circuit Fail 225 General Alarm 1 226 General Alarm 2 227 General Alarm 3 228 General Alarm 4 Chapter 4 - Page 38 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 113 507 Virtual Input 7 508 Virtual Input 8 601 LED 1 602 LED 2 603 LED 3 604 LED 4 605 LED 5 606 LED 6 607 LED 7 © 2016 Siemens Protection Devices Limited Chapter 4 - Page 39 of 58...
  • Page 114 The default double bit input event buffer size is set to allow 100 events. Double bit inputs are by default returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. Chapter 4 - Page 40 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 115 The default select/control buffer size is large enough to hold 10 of the largest select requests possible. Binary outputs are by default NOT returned in a class zero interrogation. Note, not all points listed here apply to all builds of devices. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 41 of 58...
  • Page 116 Latch On Latch On Close Pulse On Demand metering reset, Latch On Pulse On write only location. Close Pulse On 88 Remote mode Latch On Pulse On Close Chapter 4 - Page 42 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 117 107 User DP Command 1. Latch Off Pulse Off Close Trip Pulse On Pulse Off Latch On Pulse On 108 User DP Command 2. Latch Off Pulse Off Close Trip © 2016 Siemens Protection Devices Limited Chapter 4 - Page 43 of 58...
  • Page 118: Counters

    Counter change event will be generated, and once generated in which class poll (1, 2, 3, or none) will the change event be reported. Chapter 4 - Page 44 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 119: Analog Inputs

    The default analog input event buffer size is set 30. The analog input event mode is set to Most Recent, only most recent event for each point is stored. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 45 of 58...
  • Page 120: Additional Settings

    Unsolicited Events set to Enabled. Setting is only visible DNP3 when any port Application 5, 6 ... 299, 300 As Required Protocol is set to Timeout DNP3. Chapter 4 - Page 46 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 121: Not Applicable

    Chapter 4 - 7SR157 · Data Communications Definitions 6. Not Applicable This section intentionally left blank. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 47 of 58...
  • Page 122 7SR157 Technical Manual Chapter 4 - Page 48 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 123: Iec61850 Protocol Support

    For further details refer to the following publications: • Model Implementation Conformance Statement (MICS) • Protocol Implementation Conformance Statement (PICS) • Protocol Implementation Extra Information for Testing (PIXIT) © 2016 Siemens Protection Devices Limited Chapter 4 - Page 49 of 58...
  • Page 124 7SR157 Technical Manual Chapter 4 - Page 50 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 125: Serial Modems

    Where this is not possible the local modem should be set with settings equivalent to those of the remote modem as described above. © 2016 Siemens Protection Devices Limited Chapter 4 - Page 51 of 58...
  • Page 126 7SR157 Technical Manual Chapter 4 - Page 52 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 127: Configuration

    Reydisp software Communications Editor tool. The Communications Editor is provided to allow its users to configure the Communication Protocol's Files in Reyrolle brand Relays manufactured by Siemens Protection Devices Limited (SPDL). The editor supports configuring DNP3, IEC60870-5-103, IEC60870-5-101 and MODBUS protocols.
  • Page 128 Instruments menu. The user must ensure when naming the file, they use a unique file name including the version number. Please refer to the Communications Editor User Guide for further guidance. Chapter 4 - Page 54 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 129: Glossary

    When connecting relays in an optical ring architecture, the data must be passed from one relay to the next, therefore when connecting in this method all relays must have the Data Echo ON. EN100 Siemens' Ethernet communications module supporting IEC61850, available in optical and electrical versions. Ethernet A computer networking technology.
  • Page 130 Bit (logical 1) sent to signify the end. Universal Serial Bus standard for the transfer of data. Wide Area Network. A computer network covering a large geographic area. Chapter 4 - Page 56 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 131 Com1-Mode = Remote Com2 (USB) when Com2-Mode = Local when Com2-Mode = Remote Fascia Historical Information Waveform Records Event Records Fault Information Setting Information Fig. A1 Operating Mode Table © 2016 Siemens Protection Devices Limited Chapter 4 - Page 57 of 58...
  • Page 132 Tyne and Wear NE31 1TZ United Kingdom For enquiries please contact our Customer Support Centre Tel.: +49 180/524 8437 (24hrs) Fax.: +49 180/524 2471 E-Mail:support.ic@siemens.com www.siemens.com/reyrolle Template Revision 16. Chapter 4 - Page 58 of 58 © 2016 Siemens Protection Devices Limited...
  • Page 133 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 134 Figure 4-4 E6 Case Terminal Arrangement viewed from rear ................10 Figure 5-1 7SR157 Connection diagram ........................ 11 Figure 6-1 RS485 Data Communications connections between relays ..............13 Chapter 5 - Page 2 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 135: Section 1: Installation

    On receipt remove the relay from the container in which it was received and inspect it for obvious damage. It is recommended that the relay not be removed from its case. If damage has been sustained a claim should be immediately be made against the carrier, also inform Siemens Protection Devices Limited, and the nearest Siemens agent.
  • Page 136: Environmental Protection Hints

    When disposing of or transferring a mobile storage device, Siemens strongly recommends physically destroying it or completely deleting data from the mobile storage device by using a commercially available computer data erasing software.
  • Page 137: Section 2: Equipment Operating Conditions

    Front Cover The front cover provides additional securing of the relay element within the case. The relay cover should be in place during normal operating conditions. © 2018 Siemens Protection Devices Limited Chapter 5 - Page 5 of 18...
  • Page 138: Section 3: Dimension And Panel Fixings

    Typical FRONT when SIDE VIEW VIEW fitted 25mm MIN CLEARANCE FOR TERMINAL WIRING 98.5 PANEL CUT- Figure 3-1 Dimensions and Panel Drilling for Size E4 Epsilon Case Chapter 5 - Page 6 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 139 Figure 3-2 Dimensions and Panel Drilling for Size E6 Epsilon Case Hardware Model Net Weight Kg 7SR157 E4 Case 7SR157 E6 Case 3.65 Additional Transport packaging: add 0.4kg © 2018 Siemens Protection Devices Limited Chapter 5 - Page 7 of 18...
  • Page 140: Fixings

    4 off M4 Lock Washer Typical rear terminal block fixing kit (1kit per terminal block fitted to relay) comprises: • 28 off M4, 8mm Screws • 28 off M4 Lock Washer Chapter 5 - Page 8 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 141: Section 4: Rear Terminal Drawings

    2) RS485 (Block B Terminals: 14, 16, 18, 20) - connection to this communication facility is by screened, twisted pair cable. On site when wiring other facilities, ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant. © 2018 Siemens Protection Devices Limited Chapter 5 - Page 9 of 18...
  • Page 142 Figure 4-3 E4 Case Terminal Arrangement viewed from rear Ethernet Comms Input Connectors To withdraw relay check rear ethernet positions are clear and remove retaining screw Figure 4-4 E6 Case Terminal Arrangement viewed from rear Chapter 5 - Page 10 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 143: Section 5: Connection/Wiring/Diagrams

    BI = Binary Input, BO = Binary Output Data Comms Shows contacts internal (optional) to relay case assembly. Contacts close when relay chassis withdrawn from case Figure 5-1 7SR157 Connection diagram © 2018 Siemens Protection Devices Limited Chapter 5 - Page 11 of 18...
  • Page 144: Voltage Transformer Configurations

    Configuration Vbn line, 25 Check Sync, Vbn bus, 60 VTF V Line V Bus Vab line, 25 Check Sync, Vab bus, 60 VTF V Line V Bus Chapter 5 - Page 12 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 145: Section 6: Data Communications Connections

    Rear terminals twisted pair twisted pair To Control RS485 Twisted pair screened cable System Bus Termination Polarity RS485 RS485 RS485 Figure 6-1 RS485 Data Communications connections between relays © 2018 Siemens Protection Devices Limited Chapter 5 - Page 13 of 18...
  • Page 146: Additional (Optional) Ethernet Connection For Iec 61850

    Ch n Ch 1 Ch 2 62.5/125 µm fibre optic with Duplex LC connectors or RJ45 electrical connectors Figure: 6.2-2 Ethernet connection for IEC 61850 (ring connection) Chapter 5 - Page 14 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 147: Ethernet Network Redundancy Iec 61850

    RSTP need to be enabled on the device within Reydisp Manager (See Reydisp Manager userguide). Network rings with up to 30 devices is possible. Figure: 6.3-1 RSTP Ethernet Network Ring Configuration © 2018 Siemens Protection Devices Limited Chapter 5 - Page 15 of 18...
  • Page 148: Prp - Parallel Redundancy Protocol

    No reconfiguration time is necessary for the network, as is the case for RSTP. PRP need to be enabled on the device within Reydisp Manager (See Reydisp Manager userguide). Figure: 6.3-2 PRP Ethernet Network Configuration Chapter 5 - Page 16 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 149: Hsr - High Availability Seamless Redundancy Protocol

    HSR needs to be enabled on the device within Reydisp Manager (See Reydisp Manager user guide). Network rings with up to 50 devices is possible. Figure: 6.3-3 HSR Ethernet Network Ring Configuration © 2018 Siemens Protection Devices Limited Chapter 5 - Page 17 of 18...
  • Page 150 7SR157 Technical Manual Chapter 5 - Page 18 of 18 © 2018 Siemens Protection Devices Limited...
  • Page 151 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 152 Section 3: Control & Logic Functions ........................ 12 3.1 Quick Logic ............................. 12 Section 4: Testing and Maintenance ......................... 13 4.1 Periodic Tests ..........................13 4.2 Maintenance ........................... 13 4.3 Troubleshooting ..........................14 ©2016 Siemens Protection Devices Limited Chapter 6 - Page 2 of 14...
  • Page 153: Section 1: Common Functions

    The secondary injection equipment should be appropriate to the protection functions to be tested. Additional equipment for general tests and for testing the communications channel is: Portable PC with appropriate interface equipment. Printer to operate from the above PC (Optional). Chapter 6 - Page 3 of 14 ©2016 Siemens Protection Devices Limited...
  • Page 154: Use Of Pc To Facilitate Testing

    Check that the relay is correctly programmed and that it is fully inserted into the case. Refer to Section 2: Settings and Instruments for information on programming the relay. ©2016 Siemens Protection Devices Limited Chapter 6 - Page 4 of 14...
  • Page 155: Secondary Injection Tests

    The timers are also used to ensure correct operation of Binary Inputs from AC voltage energisation. If a delayed pickup is required, this must be provided by additional Quick Logic configuration. An example is shown in Chapter 7 – Applications Guide. Chapter 6 - Page 5 of 14 ©2016 Siemens Protection Devices Limited...
  • Page 156: Binary Outputs

    The operation of these contacts should be checked. Binary Output 1 terminals 1 & 2 Alarm Checked? Binary Output 2 terminals 5 & 6 Alarm Checked? ©2016 Siemens Protection Devices Limited Chapter 6 - Page 6 of 14...
  • Page 157: Section 2: Control Functions

    CS Out. Repeat this test having effectively reversed the direction of slip between Line and Bus. The results should fall within the claims made in the relevant sections of: Chapter 3 - Performance Specification. Chapter 6 - Page 7 of 14 ©2016 Siemens Protection Devices Limited...
  • Page 158: Timer Tests

    1.33s recorded time between the in-phase nominal volts being applied to the relay and 25 Check Sync being raised. This shows that the actual time is 1.01s. ©2016 Siemens Protection Devices Limited Chapter 6 - Page 8 of 14...
  • Page 159: Repeat The Test For A Range Of Check And System Sync Timer Settings

    Individually ramp up and down the Line and Bus voltages to values above and below the 25 Dead Line, 25 Live Line, 25 Dead Bus and 25 Dead Bus settings. All results should fall within the claims made in the relevant sections of: Chapter 3 - Performance Specification. Chapter 6 - Page 9 of 14 ©2016 Siemens Protection Devices Limited...
  • Page 160: Undervoltage Detector Tests

    All results should fall within the claims made in the relevant sections of: Chapter 3 - Performance Specification. Setting (%) Pick Up (%) Drop Off (%) 25 Line Undervolts 25 Bus Undervolts Note: 25 Bus Undervolts and 25 Line Undervolts have 3% hysteresis on drop-off. ©2016 Siemens Protection Devices Limited Chapter 6 - Page 10 of 14...
  • Page 161 Chapter 6 - 7SR157 Commissioning and Maintenance Guide Chapter 6 - Page 11 of 14 ©2016 Siemens Protection Devices Limited...
  • Page 162: Section 3: Control & Logic Functions

    Quick Logic equations should be tested conjunctively with connected plant or by simulation to assess suitability and check for correct operation on an individual basis with tests specifically devised to suit the particular application. ©2016 Siemens Protection Devices Limited Chapter 6 - Page 12 of 14...
  • Page 163: Section 4: Testing And Maintenance

    Relay failure will be indicated by the Protection Healthy LED being off or flashing. A message may also be displayed on the LCD. In the event of failure, Siemens Protection Devices Ltd. (or one of its agents), should be contacted.
  • Page 164: Troubleshooting

    If the above checklist does not help in correcting the problem please contact the local Siemens office or contact PTD 24hr Customer Support: Tel: +49 180 524 7000. Fax: +49 180 524 2471 or email: support.energy@siemens.com.
  • Page 165 Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent.
  • Page 166 Figure 4-2 LED configuration via the LED Matrix tab ..................14 Figure 4-3 LED configuration via the Settings \ OUTPUT CONFIG \ LED CONFIG menu ........14 Chapter 7 - Page 2 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 167: Section 1: Introduction

    This feature is implemented using internal logic and removes the need for an external guard relay. © 2016 Siemens Protection Devices Limited Chapter 7 - Page 3 of 14...
  • Page 168: Section 2: Control Functions

    Group 2. The group selection and thus the actual relay mode of operation could then be changed remotely using a status input signal or a communications command from a control system. Chapter 7 - Page 4 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 169: Manual Synchronising

    (incoming) or bus (running) voltages, which could overstress the electrical systems. Typically, the differential voltage element is set below 10% of rated voltage. © 2016 Siemens Protection Devices Limited Chapter 7 - Page 5 of 14...
  • Page 170: Synchronising Bypass Logic

    This would mean that the incoming vector could pass through the valid close window too quickly and not allow the slip timer to time out and give a valid output. Chapter 7 - Page 6 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 171: Check Synchronising Settings

    Timer settings (sec) Limit (mHz) ± 10° 0.27 102.88 ± 15° 0.42 99.21 ± 10° 0.11 252.53 ± 15° 0.17 245.10 Table 3 - Typical System Synchronising Settings © 2016 Siemens Protection Devices Limited Chapter 7 - Page 7 of 14...
  • Page 172: Example Setting Calculations For 25 Check Sync Timer

    160ms total delay time is given by, θ ∆ × × Slip = 0.083 x 360 x 0.16 = 4.80°. RELAY Therefore the CB will close at 24° + 4.80° = 28.80°. Chapter 7 - Page 8 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 173: Section 3: Supervision Functions

    BI = 19V (30, 48, 110, 220V supply) BI = 88V (110, 220V supply) BO 1 BO n R = 3K3 typical Remote Alarm Figure 3-1 Close Circuit Supervision Scheme © 2016 Siemens Protection Devices Limited Chapter 7 - Page 9 of 14...
  • Page 174: Section 4: Common Functions

    An ac supply operated BI is required to operate the System Sync inhibit function, but also include a 100ms minimum pick-up delay and 200ms minimum drop-off delay. 1) Set BI 1 for ac operation: Chapter 7 - Page 10 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 175 3) Set equation E1 to operate virtual I/O V1 in the Output Matrix: 4) Set virtual I/O V1 to operate the System Sync inhibit in the Input Matrix: © 2016 Siemens Protection Devices Limited Chapter 7 - Page 11 of 14...
  • Page 176: Use Of Binary Inputs In Control And Tripping Circuits

    Fitting these components will raise the current required to operate the BI, and hence makes it less susceptible to maloperation. Where required, the minimum pickup delay for the BI is stated on the diagram. Chapter 7 - Page 12 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 177 Resistors must be wired with crimped connections as they may run hot Figure 4-1 Example BI configurations with compliance to EATS 48-4 Classes ESI 1 and ESI2 © 2016 Siemens Protection Devices Limited Chapter 7 - Page 13 of 14...
  • Page 178: Binary Outputs

    NB: If a LED number is not assigned that particular LED will not illuminate. Figure 4-3 LED configuration via the Settings \ OUTPUT CONFIG \ LED CONFIG menu Chapter 7 - Page 14 of 14 © 2016 Siemens Protection Devices Limited...
  • Page 179 Siemens Protection Devices...
  • Page 180 Siemens Protection Devices Limited P.O. Box 8, North Farm Road Hebburn, Tyne & Wear NE31 1TZ United Kingdom Phone: +44 (0)191 401 7901 Fax: +44 (0)191 401 5575 E-mail: marketing.spdl.gb@siemens.com For enquires please contact our Customer Support Center Phone: +49 180/524 8437 (24hrs)