Eltek Valere Flatpack2 Quick Start Manual page 7

Hide thumbs Also See for Flatpack2:
Table of Contents

Advertisement

Connections, Factory Settings, etc
The schematic shows the connection terminals in Smartpack2-based Flatpack2 PS Systems with
4U DC Distribution. Or refer to specific drawings included with your system.
Smartpack2 Basic controller
(These multipurpose inputs may also be used as digital inputs,
e.g. for SPD monitoring)
For installations in USA and Canada only!
– The installation has to comply with the NEC/CEC requirements
– The distribution can only be used as a branch circuit distribution, if the circuit
breakers are UL489 (DITT) certified.
–For supply connectors, use wires suitable for at least 75˚C (167˚F), type: FEPW,
RH, RHW, THHW, THW, THWN, ZHHW, USE, ZX or similar. Use copper
conductors only
For installations
in USA and Canada only!
External AC Output Wires
Recommended Ratings
Current
Wire Section
2)
Max. (A)
(mm
(AWG)
6
0.75
10
1.0
13
1.5
16
1.5
20
4
25
6
32
6
40
10
50
16
63
25
Recommendations if used as branch
circuits. Based on 45˚C ambient
(factor 0.82)
For installations
outside USA and Canada!
External AC Input Wires
Recommended Ratings
Current
Wire Section
2)
Max. (A)
(mm
(AWG)
6
0.75
18
10
1.00
16
13
1.25
16
16
1.50
14
25
2.50
12
32
4.00
10
40
6.00
8
63
10.00
6
80
16.00
4
100
25.00
2
The figure shows the position of the relay contacts
when the PS system is in alarm mode of operation;
the relay coils are then de-energized (fail-safe
mode). The relay outputs are preprogrammed from
factory (Factory Settings).
Quick Start Guide Flatpack2 PS System, 4U, SP2-based
Flatpack2 System, Integrated
4U DC Distr. with SP2 Ctrls
FUNCTION
SIGNAL PIN-OUT
X:**
1
+
Temp Sense 1
2
3
+
Temp Sense 2
4
5
+
Temp Sense 3
6
Max. 1.5 mm
(14
) wire section
AWG
For installations
in USA and Canada only!
External DC Output Wires
Recommended Ratings
Current
Wire Section
2)
Max. (A)
(mm
18
1
0.75
16
2
0.75
14
4
0.75
14
5
0.75
10
6
0.75
8
10
1.0
8
15
1.5
6
16
1.5
4
20
2.5
3
25
4
30
6
32
6
40
6
50
10
60
16
63
16
Recommendations if used as branch
circuits
FUNCTION
Temperature
Sensor 1
Temperature
Sensor 2
Temperature
Sensor 3
2
,
Fb1
Fb2
(AWG)
Common DC Output &
18
18
18
I/O Monitor2 CAN Node
18
18
16
Config. Input
14
14
12
Config. Input
10
8
Config. Input
8
8
6
Config. Input
4
4
Config. Input
Config. Input
Common Alarm
Mains Alarm
Fuse Alarm
Load & Battery
High Battery Alarm
Low Battery Alarm
Rectifier Alarm
356825.103, 2v0 -2011-09
Installation
SIGNAL
TERM. POINT
X:*
L3
7
L2
6
L1
5
4
N
3
2
PE
1
(For Mains wiring reconfigu-
PE
ration, see section
(Protective
"Miscellaneous")
Earth)
Load Circuit 1
F1
Load Circuit 2
F2
Load Circuit 3
F3
Load Circuit 4
F4
Load Circuit x
Fx
Battery Cables, string 1
Battery Cables, string x
(Only used in Flatpack2
systems with external battery
Battery Rails
bank)
X:***
Input Circuit 1
1
+
Input Circuit 2
2
+
Input Circuit 3
3
+
Input Circuit 4
4
+
Input Circuit 5
5
+
Input Circuit 6
6
+
X:****
Relay 1
NO
C
Alarm Circuit 1
NC
Relay 2
NO
C
Alarm Circuit 2
NC
NO
Relay 3
C
Alarm Circuit 3
NC
Relay 4
NO
C
Alarm Circuit 4
NC
Relay 5
NO
C
Alarm Circuit 5
NC
Relay 6
NO
C
Alarm Circuit 6
NC
AC Mains
Cable (Y)
2
35 mm
, 1
,
AWG
max. wire section
2
16 mm
, 4
AWG
max. wire section
2
Max. 1.5 mm
,
(14
) wire section
AWG