4.2.3 Setting of trigger recording
* System 1 only is possible to set trigger recording in the TYPE 3 software.
* The [Trigger recording] is a method which records before and after meeting
trigger conditions (a combination of digital values (ON/OFF) of operation data).
(Notes)
The window of the [Trigger record setting] is displayed by pressing the button of the
[Trigger record setting(F8)] after selecting the [Recording mode(F5)] in the window of
the [Network Map Display].
Procedures
(1) Set the [1. Record time before and after trigger] and the [2. Trigger setting].
Setting item
1. Record time
before and
after trigger
2.1 Trigger
record
- 37 -
1. Since air conditioners conforming to the DIII-NET in the internal and
external transmission method will take maximum several minutes for
data-transfer intervals, triggering may be delayed several minutes even if
actual changes are taken place in an air conditioner.
2. Depending on a combination of trigger conditions, triggering may not
occur because of time deviation between the changes of an air
conditioner and its data transfer.
The window of [Trigger record setting]
When the trigger conditions are met in the window of the [2.2 Trigger
conditions setting], set a time by minute unit to determine the recording time
before and after trigger. If setting [30 minutes] for the record time, the
operation data for 30 minutes before and after trigger are recorded.
If set to a value higher than 60 minutes, the record time before trigger setting
will be set to 60 minutes and that after trigger will be set to the value.
The interval of recording to the hard disk of the personal computer is fixed
10 seconds.
System 1 only is possible to set trigger recording in the TYPE 3 software.
Select a System(each outdoor unit) recording trigger.
Description
Chapter 4 Recording of operation data
Need help?
Do you have a question about the Service Checker TYPE 3.1 and is the answer not in the manual?
Questions and answers