Turning Up Batteries; Removing Battery Cover Knockout Panel - ADC Soneplex Soneplex Fiber Hub Cabinet SPX-CABFIN04 User Manual

Soneplex fiber hub cabinet
Table of Contents

Advertisement

LTPS-UM-8007-01, Issue 1
26
Place the protective plastic covers on the battery.
27
Ensure that all battery cables are dressed to clear the opening as the drawer is closed.
Do not install the battery drawer cover at the front of the battery drawer at this time.
T
U
B
URNING
P
ATTERIES
Before starting this procedure, verify that the rectifier modules have not been installed, or are
turned off. If the rectifier modules are powered up, DMM indications will show rectifier output
instead of battery voltage.
A Fluke 79 Digital Multimeter (DMM) and TL20 Industrial Test Lead Set (or equivalent) are needed
to complete this procedure.
1
Verify that all batteries are properly installed.
2
If the batteries:
are in one 6V string, proceed to Step 4.
are in two 12V strings, continue with Step 3.
3
Isolate the first and second battery strings:
At the DC distribution panel, operate the battery disconnect (by inserting the pin provided at the
right-hand side into the BATTERY DISCONNECT jack shown in
Disconnect any one connector from the battery connector bus for the second string of batteries.
SPX-CABFIN01, SPX-CABFIN04
Figure 29. Removing Battery Cover Knockout Panel
November 9, 2001
Remove the middle panel on
one side with pliers, flex
the panel until it snaps off.
Figure 30 on page
36), or:
Installation