Installation
Chloride PowerSafe batteries have a red disc below the positive (+) terminal and a blue disc
below the negative (-) terminal.
16
If the cabinet:
Is not equipped with a BTRM System, proceed to Step 19.
Is equipped with a BTRM System, continue with Step 17.
17
Locate the bag of eight TSUs in the loose parts kit.
The TSUs (about 3/4 in. diameter) are labeled 428804800 60°C.
18
Install a TSU on the negative terminal.
One TSU is to be installed at each battery negative post.
For details, refer to Lorain Products Installation Instructions.
19
Install the flat washer and lock washer, and install (but do not tighten) the terminal fastener (screw or nut).
20
Position the battery cable ends as shown in
to a torque of 65-70 in-lb (735-790 [N-cm]) maximum.
Negative
terminal
32
Figure 25
Lock washer
Figure 25. Battery Cable Installation of Stud Terminal
November 9, 2001
or
Figure 26 on page
33. Tighten both battery terminals
Hex nut
LTPS-UM-8007-01, Issue 1
Flat washer
TSU
Positive
lead
Anderson
connector
Negative
lead
SPX-CABFIN01, SPX-CABFIN04