4.13. EMC Compliant Installation
4.13.1. Recommended Installation for EMC Compliance
Fuse /
MCB
L1
L2
L3
PE
Mains - supply
4
4.13.2. Recommended Cable Types by EMC Category
Number of
Input Phases
1
3
3
NOTE
 Data in brackets shows permissible cable length with additional external EMC filter.
 The 500 – 600V drives are not equipped with the internal EMC filter and are intended for use on second environment only.
28 | Optidrive P2 User Guide | Version 3.07
≥ 100mm
Control cables
Rated Supply
Frame Size
Voltage
230
2
2, 3
4, 5
230
4,5
6A, 6B
6, 7
2, 3
4, 5
4,5
400
6A, 6B
6, 7
8
Mounting plate
with conductive
surface
For Best-Practice use
360° bonding EMC
cable gland shielded
to motor chassis.
Cable shield exposed
and 360° clamped to
grounded metal plate or PE
bar. All other 360° bonding
methods are acceptable.
Motor cable
3-phase and PE shielded cable.
Maintain shield as far as
possible along the cable
Maximum Motor Cable Length to Achieve
IP rating
C1
IP20, IP66
IP20, IP66
IP20, IP55
IP55
IP20
IP55
IP20, IP66
IP20, IP55
IP55
IP20
IP55
IP20
Control cables
Twisted-Pair shielded
cables for analog
control and motor
feedback signals.
U V W PE
C2
1, 2, 5, 6, 8
3, 5, 6, 8
1 (5)
5 (25)
1 (5)
5 (25)
1 (5)
5 (25)
-
-
-
100
-
-
1 (5)
5 (25)
1 (5)
5 (25)
-
-
-
100
-
-
-
-
www.invertekdrives.com
C3
4, 7, 8
25 (100)
25 (100)
25 (100)
25 (100)
100
25 (100)
25 (100)
25 (100)
25 (100)
100
25 (100)
25